Wiring
975-0289-01-01
3–15
DC Wiring with Ground Fault Protection
(Renewable Energy Solar Panel; Maximum 400 W)
Important:
Renewable energy input may require additional hardware to be
code-compliant. There may also be additional grounding requirements. Be sure
to consult your local electric authority for additional requirements.
Figure 3-14
Connecting the DC Input (Renewable Energy Solar Panel)
Example only. Actual installation may vary.
Torque Neutral and Line terminals
to 1.3 nm (11.5 in-lbs)
Torque Ground terminal
to 1.8 nm (16.0 in-lbs)
Torque Positive, Negative, and
Ground terminals to
20.3 nm (180 in-lbs)