Specifications
A–10
975-0334-01-01
Adjustable Voltage, Frequency and Reconnection Settings
Utility disconnect settings can be adjusted using the GTConfigLite software tool.
Permission of the utility must be granted before adjusting any of these settings.
For more information about installing and using GTConfigLite, see the
GTConfigLite
User’s Guide
(p/n 976-0260-01-01), available with the software.
Setting
Default
Tolerance
Adjustment Range
Low
High
Tolerance
Phase-to-Neutral (rms) High Threshold
Voltage
131.50
+0.5, –2.5 V 130.50 135.00
±1.5 V
Phase-to-Neutral (rms) Reconnect
Voltage
126.96
±0.24 V
126.96 135.00
±1.5 V
Phase-to-Neutral (rms) Low Threshold
Voltage
106.10
–0.5, +2.5 V 102.00 107.10
±1.5 V
Voltage (rms) High Clearing Time (ms) 1000
+0, –0.1 s
1000
2000
+0, –0.1 s
Voltage (rms) Low Clearing Time (ms) 2000
2000
5000
Frequency High Threshold
60.40
±0.1 Hz
60.40
60.60
±0.1 Hz
Frequency Low Threshold
59.40
57.00
59.80
Frequency High Clearing Time (ms)
160
+0, –0.1 s
160
200
+0, –0.1 s
Frequency Low Clearing Time (ms)
160
160
300000
Reconnect Delay (ms)
305000
n/a
60000
305000 n/a