Cable Installation
152602
2–5
Cable Installation
Wire Gauge and Torque Specifications
The following torque specifications are to be used on all electrical
interfaces made during installation of the GT100E MS Combiner Box.
Wire Gauge Requirements for the GT100E MS Combiner Box
One or multiple wires up to 300 mm2 can be connected to the GT100E
MS Combiner box. Follow local Electrical codes to determine the correct
wire gauge.
Torque Specifications for the GT100E MS Combiner Box
M10 Bolt
40.0Nm
M12 Bolt
54.0Nm
M16 Bolt
132.0Nm
CAUTION
All wiring methods and wire gauges shall be in accordance with Local Electrical
Code. Take care to keep the wire bundles away from any sharp edges which may
damage wire insulation over time.