Basic Installation Procedures
975-0799-01-01
29
8. Connect each AC wire into its corresponding terminal on the
no-tool cage clamp terminal block.
a. Lift the terminal lever (as shown in the previous figure).
b. Insert the wire fully into the open slot.
c. Lower the terminal lever to secure the wire in the slot.
9. Make sure that each AC wire is matched and connected to
the Neutral (
N
), Ground (
G
), and Line (
L
) connections.
10. Tighten the strain relief clamp to secure the wires.
11. Replace the wiring compartment cover onto the unit (using a
#2 Phillips torque screwdriver - see WARNING), if you are
not connecting other wires such as for the AC Output.
Otherwise, keep the AC compartment open and proceed to
the next step.
WARNING
ELECTRICAL SHOCK HAZARD
Use a torque screwdriver to tighten the captive nut panel screw to
5 in-lb torque of force to ensure a proper ground connection and a
required tool access to the wiring compartment.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
12. Connect the other end of the wires to the circuit breaker in
the AC distribution panel supplying AC power to the unit.
Step 5: Connecting AC Output to an
Existing AC Circuit
WARNING
ELECTRIC SHOCK AND FIRE HAZARDS
Make sure wiring is disconnected from all electrical sources before
handling. All wiring must be done in accordance with local and
national electrical wiring codes.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
NOTICE
EQUIPMENT DAMAGE
l
Do not connect any AC source (such as a generator or
utility power) to the AC output wiring of the Freedom XC
PRO.
l
The Freedom XC PRO will not operate if its output is
connected to AC voltage from another source, and
potentially hazardous or damaging conditions may occur.
These conditions can occur even if the inverter/charger is
off.
Failure to follow these instructions can result in equipment
damage.