Operating During Transition Between Grid Mode and Battery Mode
975-0799-01-01
73
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Transfer Mode
11
APL
APL
(appliance)
UPS
(UPS)
Selecting
APL
- appliance sets the transfer time from line to battery
to 20 ms. Selecting
UPS
(uninterruptible power supply) sets the
transfer time from line to battery to 10 ms.
NOTE
: Do not connect
motor loads when in UPS transfer mode. See
Utility AC Under Voltage
Level
12
90
85
to
110
Inverter Shutdown
Recovery
13
MAT
At0
(auto-
restart)
MAT
(manual
restart)
The inverter shuts down when there is an over temperature,
overload, and short circuit condition. Selecting
ATO
(auto-restart)
will allow the inverter/charger to recover automatically from a
shutdown up to three times maximum. Selecting
MAT
(manual
restart) allows the user to restart the inverter/charger by performing
a manual reset, that is, by acknowledging the restart via the
display panel.
Audible Alarm
14
bON
bON
Audible
BOF
(Mute)
The alarm beeps once every five seconds.
Battery Type
20
FLD
FLDFlooded
AGM
(AGM),
GEL
Gel
USE
(Custom)
LFP
(LiFePO
4
The use of
LFP
(LiFePO
4
)as a battery type requires a compatible
BMS. See
for safety warning instructions.