975-0697-01-01
67
Specifications
This guide for use by qualified installers only.
NOTE
: All transfer specifications are at nominal conditions: ambient temperature of 25 °C, 230 VAC, 50 Hz input, unless
otherwise specified.
Transfer and General
Specifications
All Models
Transfer time—utility to invert
< 20 ms
Minimum AC input voltage for transfer
170 VAC
Maximum AC input voltage for transfer
270 VAC
Minimum AC input frequency for transfer
45 Hz
Maximum AC input frequency for transfer
68 Hz
Cooling
Fan-cooled, temperature controlled.
Regulatory Approvals
All Models
Safety
CE mark (Europe)
EN62040-1
RCM mark (Australia)
AS 62040.1.1
AS/NZS 60335.2.29
EMC
CE (Europe) and RCM (Australia)
EN 62040-2
FSW 230V Installation Guide.book Page 67 Tuesday, August 7, 2018 9:18 AM