Installation
1–20
975-0046-01-01
To make the neutral connections:
1. Create only one neutral-to-ground bond in the system. In this case, it
would be in the main AC distribution panel.
2. Connect the neutral (white) wire from neutral bar in the AC
distribution panel to one of the neutral terminals in the
ACCB
.
3. Connect the factory-installed neutral wire (white) in the
ACCB
to the
NEU2 terminal in the inverter.
4. Connect the neutral (white) wire from the generator and connect it to
one of the neutral terminals in the
ACCB
.
Important:
Ensure there is only one neutral-to-ground bond in the entire
system. See the Sine Wave Plus Inverter/Charger Owner’s Manual for additional
information regarding the neutral-to-ground bond requirements.
Figure 1-16
Neutral Connections for an Off-Grid Application with an AC Distribution Panel
and an External Generator Disconnect