background image

Page 2

Congratulations!  You have just purchased the best quality powerline carrier
lighting module available.  X-10 PRO's Lighting Module is a high quality, X-10
compatible product that is a low cost alternative to hard-wired lighting systems.

This booklet covers all X-10 PRO models XP4LS and XP1LS.

CAUTION!!

READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING DEVICE.

This device is intended for installation in accordance with the National Electric Code
and local regulations.  It is recommended that a qualified electrician perform this
installation.  

Retain these instructions for future reference.

To reduce the risk of overheating and possible damage to other equipment, do not
install dimming versions to control a receptacle, a motor-operated appliance, a
fluorescent lighting fixture, or a transformer-supplied appliance. This product is for
indoor use only.  Connect only copper or copper clad wire to this device.

Pour re'duire le risque d'augmenter la chaleur des diffe'rents equipments, ne pas
installer une piece de control, une machine `a moteur, une fixture fluorescente or un
transformateur.

INSTALLATION

Installation Notes

a.   Be sure that power to the supply circuit has been disconnected by removing fuse or

turning circuit breaker off.  Installing the module with power on may expose you to
dangerous voltages and may damage the device.

Installation Procedures

1.   Install a standard 4 gang box or RACO 953 box, pre-wire for power, loads, remote

switch, and transmitter controls.

2.   Power should be a 20 circuit directly from a breaker 2x12ga wire and ground.

3.   Load, remote switch, and transmitter circuits should each be connected via separate

sets of two 14ga wire with ground.

4.   Using a voltage tester, identify and mark the “Hot” and the “Neutral” wires.

5.   Identify and label each pair of load and control point wires.

6.   If setting up an X-10 PRO lighting system enter the appropriate circuit labels and

addresses in the programming manual worksheets and on the module labels.

7.   After all connections have been made, be certain all wire connectors are firmly

attached and there are no exposed wires (except the bare ground wire).

8.   Place wires and insert into wall box and screw unit into place with supplied screws.

Four gang box uses four or eight 6x32x1/2 screws, Raco 953 box uses  four
8x32x1/2 screws.

Summary of Contents for X10 PRO XP1LS

Page 1: ...Power Lighting Module INSTALLATION AND OPERATING INSTRUCTIONS For Models XP4LS XP1LS 10012 North Dale Mabry Ste 115 Tampa FL 33618 Tel 800 TECH 003 Fax 813 265 1011 Email x10protec x10pro com Web www...

Page 2: ...ur une fixture fluorescente or un transformateur INSTALLATION Installation Notes a Be sure that power to the supply circuit has been disconnected by removing fuse or turning circuit breaker off Instal...

Page 3: ...ght circuit via the Lighting Module control inputs Wiring Notes a Remote switches require a Line Voltage input Black that is always hot Do not connect to the load switched circuit b The gray wire on t...

Page 4: ...t for simple and inexpensive installation The home run wiring scheme is very different than conventional wiring methods The conventional way typically taps off or daisy chains as many fixture switch s...

Page 5: ...control devices including those manufactured by PCS Lutron Lightolier Leviton X 10 and ACT d provides ample wiring room for large number of wire nut connections often required e circuits can be easil...

Page 6: ...is is the normal operating state of the Lighting Module Mode 1 mode used to set primary address of the channel s Mode 2 mode used to set scene addresses to the scene numbers Mode 3 mode used enable or...

Page 7: ...are in Mode 5 Setting Advanced Programming Options LED Color Indicator Program Mode Mode Name LED Pattern Normal Operation Solid Red Mode 1 Setting New Primary Address Blinking Green Mode 2 Setting Ne...

Page 8: ...nnel numbers 1 through 4 MM2s have channel numbers 1 and 2 SS1s have only channel number 1 5 Press the ON key or OFF key Pressing ON or OFF key will determine if the channel will respond or not respon...

Page 9: ...mber 1 5 Press the ON key or OFF key Pressing ON or OFF key will determine if the channel will respond or not respond to the Scene Address 6 Press All Lights On key The product stores new setting into...

Page 10: ...rogramming mode and into normal operation Numbered Key on Transmitter Controller Advanced Programming Option Default Setting 1 Soft Start Enabled 2 All Lights On Enabled 3 All Lights Off Enabled 4 All...

Page 11: ...IME ADDR LIGHTING LEVELS Ch 1 Channel 1 A1 100 70 40 20 100 70 40 20 100 70 40 20 100 70 40 100 Ch 2 Channel 2 A2 100 70 40 20 100 70 40 20 100 70 40 20 100 70 40 100 Ch 3 Channel 3 A3 100 70 40 20 10...

Page 12: ...ypes Incandescent Magnetic Low Voltage Incandescent Magnetic Low Voltage Input Power 125 VAC 125 VAC Min Load 60 W 60 W Min Receive Level 5 mV 5 mV Max Noise Rejection 350 mV 350 mV Connections 16 AWG...