4.3 Allocation of a room control unit to a heating zone (pairing)
4.4 Performing the radio test
¾
Press the rmBUS button of the base station for three seconds in order to start the pairing mode.
9
The LED “Heating zone1” flashes.
¾
Select the desired heating zone by pressing shortly again.
9
For three minutes, the selected heating zone is ready to receive the pairing signal of a room control
unit.
¾
Activate the pairing function at the room control unit (see Room Control Unit Manual).
9
The pairing mode is left after establishing a successful allocation.
9
The LED of the heating zone previously selected will light up for 1 minute.
¾
Repeat the process for allocating more room control units.
Tip
One Room Control Unit can be allocated to various heating zones.
The allocation of several room control units to one zone is impossible.
The radio test allows to verify the communication between the base station and the room control unit. The
radio test must always be carried through at the planned installation location of the room control unit.
9
The base station must not be in pairing mode for this.
¾
Start the radio test at the room control unit (see Room Control Unit Manual).
9
The heating zone allocated to the room control unit is activated for one minute, thus it is switched off or
on depending on the status of operation.
9
If there is no activation, the reception conditions are unfavourable. Proceed as follows:
¾
Taking into account the installation conditions of the room control unit, change the installation posi-
tion until you have a reception signal, or
¾
Use the optional accessories “Active antenna” or “Repeater” in order to amplify the radio signal.
You can find information on the installation in the respective manual.
4.2 Connecting (pairing) / separating base stations (continued)
The separation of paired base stations can be performed as follows:
¾
Press the syBUS button of the base station to be separated for three seconds in order to start the pair-
ing mode.
9
The LED “syBUS” flashes.
¾
Press the syBUS pushbutton again for a duration of 10 seconds.
9
The base station restarts and the LED “Master” goes out.