3-5
Quick Start
b)
Text Interface:
i.
Via Telnet:
Telnet to the RPC’s default IP address
(192.168.168.168). The Circuit Status Screen (Figure 3.3)
should be displayed.
ii.
Via Local PC:
Start your communications program and then
press
[Enter]
. The Circuit Status Screen should be displayed as
shown in Figure 3.3. The default communications parameters
for the Console Port are 9600 bps, No Parity, 8 data bits, One
stop bit.
iii.
Via Modem:
Use your communications program to dial the
number for the phone line which is connected to your external
modem. Note that in order to communicate with the unit via
modem, you must first access the command mode via Network
or Local PC, and use the Serial Parameters Menu to set the Port
Mode to "Modem."
2.
Test Switching Functions:
You may wish to perform the following tests
in order to make certain that the RPC is responding to commands.
a)
Reboot Circuit:
If you are communicating with the unit via the
Web Browser Interface, select the button in the "Boot" column for
Circuit 1, and then click "Apply." If you are operating the unit via
the Text interface, type
/BOOT 1
and press
[Enter]
. The status
indicator for Circuit 1 should go off, pause for a moment, and then
go back on, indicating that the boot cycle has been successfully
completed.
b)
Switch Circuit Off:
From the Web Browser Interface, select the
button in the "Off" column for Circuit 1, and then click "Apply."
From the Text Interface, type
/OFF 1
and press
[Enter]
. The status
indicator for Circuit 1 should go Off, indicating that the command
has been successfully completed. Leave Circuit 1 in the "Off" state
for now, and then proceed to the next step.
c)
Switch Circuit On:
From the Web Browser Interface, select the
button in the "On" column for Circuit 1, and then click "Apply."
From the Text Interface, type
/ON 1
and press
[Enter]
. The status
indicator for Circuit 1 should then go back On, indicating that the
command has been successfully completed.