WDFC Quick Start Guide

Common Parameters

 (continued)

Group 

Name

Description

See drive manual for complete configuration capabilities

NOTE: Press [ESC] key to escape from a Group

Default 

Value

Value  

Range

New  

Value

CON

Control Group

CON-04

Carrier Frequency Select in kHz

3kHz

Input Terminal Group

IN90

Digital Input Status: for troubleshooting (dependent upon NO/NC Contact)

0

Output Terminal Group

OUT01

AO1 assignment: 0 = Freq; 1 = Out Amps; 2 = Out Volt; 3 = DC Bus; 4 = Pwr; 7 = Target Hz

0

OUT07

AO2 assignment: 0 = Freq; 1 = Out Amps; 2 = Out Volt; 3 = DC Bus; 4 = Pwr; 7 = Target Hz

0

OUT31

Relay 1: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV

0

OUT32

Relay 2: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV

0

OUT33

Relay 3: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV

14

OUT34

Relay 4: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV

0

OUT35

Relay 5: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV

0

OUT36

Q1 Open Collector Output Define: 0 = None; 14 = Run; 22 = Ready

0

OUT41

Digital Output Status: troubleshoot: 0 = None; 1 = FDT-1; 2 = FDT2; 3 = FDT3; 4 = FDT4

0

COM

Communication Group

AP

Application Group

AP2-15

Pump Clean Mode 1; 0 = None; 1 = DI Dependent; 2 = Output Power; 3 = Output Current

0

AP2-16

Pump Clean Mode 2; 0 = None; 1 = Start; 2 = Stop; 3 = Start & Stop

0

AP2-38

Decel Valve Freq: in Hertz

40.00

AP2-39

Decel Valve Freq: in seconds

0.0

AP3

Configures the time event related features: See manual

Protection Group

PRT04

Load Duty: 0 = Normal Duty; 1 = Heavy Duty

1

PRT05

Input/Output open phase protection: Bit low = Off; Bit high = On (See manual)

0

PRT06

Open-phase input voltage band: adjustable (See manual)

40

PRT08

Auto Restart: 0 = No; 1 = Yes: Caution - VFD may start unexpectedly

0

PRT09

Retry Number: Auto Restart number of attempts

0

PRT10

Auto Restart delay time in seconds

0.0

PRT20

Overload Trip Select: 0 = None; 1 = Free-Run; 2 = Decel

0

PRT21

Overload Trip Level

180

PRT22

Overload Trip Time

60sec

LCD Keypad Operations: Control Function Group:

CNF10

VFD Software Version

CNF20

Anytime Parameters: User display para - 0 = Freq; 1 = Speed; 2 = Out Curr; 6 = DC Bus

0

CNF21

Monitor Mode: user defined monitor items from CNF-21 - CNF-23

0

CNF24

Monitor Mode: Enable to activate CNF-20-23: 0 = Disable; 1 = Enable

0

CNF40

Factory Default reset: 0 = No; 1 = All Groups

0

CNF41

Changed Parameter: 0 = Display all parameter; 1 = Display only changed parameters

0

CNF43

Macro Selection: 0 = Basic; 1 = Compressor; 2 = Supply Fan; 4 = Cooling Tower; 7 = CT

0

CNF44

Erase trip history: 0 = No; 1 = Yes

0

CNF46

Parameter read: 1 = Read (LCD Keypad)

0

CNF47

Parameter read: 1 = Write: VFDs must be same FW Rev (LCD Keypad)

0

Note: Shaded areas above denote most frequently used parameters

Summary of Contents for WorldDrive WDFC Series

Page 1: ...pyright 2019 WorldWide Electric Corporation The Globe icon is a registered trademark of WorldWide Electric Corporation WORLDWIDEELECTRIC NET Quick Start Guide WORLDDRIVE WDFC This Quick Start Guide is...

Page 2: ...or during operation Doing so may result in serious injury death or serious property damage Do not open the cover of the VFD even when the power supply to the VFD has been turned off unless it is nece...

Page 3: ...emove screw and wiring cover 2 Wire the incoming power to terminals R L1 S L2 T L3 3 For single phase input applications use R L1 and T L3 4 Wire the motor to terminals U V W 5 Be sure to connect the...

Page 4: ...Pump 6 Vacuum Pump 7 Constant Torq Sample Motor Nameplate EzStart N STP 0 0Hz 99 Start Easy Set 0 1 No Yes D C BAS10 60 50 Hz Sel 1 0 50 Hz 60 Hz DC EzStart N STP 0 0Hz DRV14 Motor Capacity 7 5 0 HP D...

Page 5: ...e voltage Sample Motor Nameplate EzStart N STP 0 0Hz BAS13 Rated Curr 0 0 1000 0 A D 3 6 C 8 0 8 0 A EzStart N STP 0 0Hz BAS15 Rated Volt 170 480 V D 0 C 0 460V EzStart N STP 0 0Hz BAS11 Pole Number 2...

Page 6: ...On the Keypad and monitor your Speed Hz 3 Select the Off Button to stop operation VERIFY MOTOR ROTATION DRV06 Cmd Source 1 Fx Rx 1 DC 2 Fx Rx 2 0 Keypad EzStart N STP 0 0Hz DRV07 Freq Ref Src EzStart...

Page 7: ...A01 Bias 0 0 4 A01 Filter 5ms 6 A01 Monitor 0 0 7 AO2 Mode Frequency 8 A02 Gain 100 0 9 A02 Bias 0 0 10 A02 Filter 5ms 12 A02 Monitor 0 0 31 Relay 1 Trip 32 Relay 2 Run 33 Relay 3 None 34 Relay 4 None...

Page 8: ...4 V2 5 I2 6 Int485 8 Fld Bus 0 0 11 DRV09 Control Mode 0 V F 1 Slip Comp 2 Resv 3 IM Sensorless 4 PM Sensorless V F 0 4 DRV14 Motor HP size capacity 5 800 DRV15 Torque Boost 0 Manual 1 Auto 2 Auto 2...

Page 9: ...lean Mode 1 0 None 1 DI Dependent 2 Output Power 3 Output Current 0 AP2 16 Pump Clean Mode 2 0 None 1 Start 2 Stop 3 Start Stop 0 AP2 38 Decel Valve Freq in Hertz 40 00 AP2 39 Decel Valve Freq in seco...

Reviews: