WDFC Quick Start Guide
Common Parameters
(continued)
Group
Name
Description
See drive manual for complete configuration capabilities
NOTE: Press [ESC] key to escape from a Group
Default
Value
Value
Range
New
Value
CON
Control Group
CON-04
Carrier Frequency Select in kHz
3kHz
Input Terminal Group
IN90
Digital Input Status: for troubleshooting (dependent upon NO/NC Contact)
0
Output Terminal Group
OUT01
AO1 assignment: 0 = Freq; 1 = Out Amps; 2 = Out Volt; 3 = DC Bus; 4 = Pwr; 7 = Target Hz
0
OUT07
AO2 assignment: 0 = Freq; 1 = Out Amps; 2 = Out Volt; 3 = DC Bus; 4 = Pwr; 7 = Target Hz
0
OUT31
Relay 1: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV
0
OUT32
Relay 2: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV
0
OUT33
Relay 3: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV
14
OUT34
Relay 4: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV
0
OUT35
Relay 5: 0 = None; 1 = FDT1; 5 = OL; 7 = Under Load; 9 = Stall; 10 = OV; 11 = UV
0
OUT36
Q1 Open Collector Output Define: 0 = None; 14 = Run; 22 = Ready
0
OUT41
Digital Output Status: troubleshoot: 0 = None; 1 = FDT-1; 2 = FDT2; 3 = FDT3; 4 = FDT4
0
COM
Communication Group
AP
Application Group
AP2-15
Pump Clean Mode 1; 0 = None; 1 = DI Dependent; 2 = Output Power; 3 = Output Current
0
AP2-16
Pump Clean Mode 2; 0 = None; 1 = Start; 2 = Stop; 3 = Start & Stop
0
AP2-38
Decel Valve Freq: in Hertz
40.00
AP2-39
Decel Valve Freq: in seconds
0.0
AP3
Configures the time event related features: See manual
Protection Group
PRT04
Load Duty: 0 = Normal Duty; 1 = Heavy Duty
1
PRT05
Input/Output open phase protection: Bit low = Off; Bit high = On (See manual)
0
PRT06
Open-phase input voltage band: adjustable (See manual)
40
PRT08
Auto Restart: 0 = No; 1 = Yes: Caution - VFD may start unexpectedly
0
PRT09
Retry Number: Auto Restart number of attempts
0
PRT10
Auto Restart delay time in seconds
0.0
PRT20
Overload Trip Select: 0 = None; 1 = Free-Run; 2 = Decel
0
PRT21
Overload Trip Level
180
PRT22
Overload Trip Time
60sec
LCD Keypad Operations: Control Function Group:
CNF10
VFD Software Version
CNF20
Anytime Parameters: User display para - 0 = Freq; 1 = Speed; 2 = Out Curr; 6 = DC Bus
0
CNF21
Monitor Mode: user defined monitor items from CNF-21 - CNF-23
0
CNF24
Monitor Mode: Enable to activate CNF-20-23: 0 = Disable; 1 = Enable
0
CNF40
Factory Default reset: 0 = No; 1 = All Groups
0
CNF41
Changed Parameter: 0 = Display all parameter; 1 = Display only changed parameters
0
CNF43
Macro Selection: 0 = Basic; 1 = Compressor; 2 = Supply Fan; 4 = Cooling Tower; 7 = CT
0
CNF44
Erase trip history: 0 = No; 1 = Yes
0
CNF46
Parameter read: 1 = Read (LCD Keypad)
0
CNF47
Parameter read: 1 = Write: VFDs must be same FW Rev (LCD Keypad)
0
Note: Shaded areas above denote most frequently used parameters