WorldWide Electric Motor WD4X Quick Start Guide
This guide and all referenced information is intended for qualified personnel only.
For additional information, please consult the WD4X User Manual (Document No: MC-OM-4XS0618.R01)
1-800-808-2131
12
Group
Name
Description
See drive manual for complete configuration capabilities
Default
Value
Value
Range
New
Value
Control Group
Cn04
Carrier Frequency Select in kHz
2 or 3 kHz
1.0-15.0 kHz
Cn70
Speed Search modes:
0
= Flying Start-1;
1
= Flying Start-2
1
Cn71
Speed Search: affects restart after power interruption: Also Ad10 =
1
b0000
Input Terminal Group
Input selections are typically assignable for digital inputs P1 thru P5
In65
P1 Define Digital input 1:
0
= None;
1
= FX;
2
= RX;
3
= RST;
4
= Ext Trip;
5
= BX;
6
= Jog
1
0-52
In66
P2 Define Digital input 2:
7
= Speed L;
8
= Speed M;
9
= Speed H;
13
= Run Enable
2
0-52
In67
P3 Define Digital input 3:
14
= 3-wire;
15
= 2nd Source;
17
= Up;
18
= Down
5
0-52
In68
P4 Define Digital input 4:
23
= Open Loop;
26
= 2nd Motor;
34
= Pre-Excite
3
0-52
In69
P5 Define: Digital input 5:
38
= Timer in;
46
= Fwd Jog;
50
= User Seq;
51
= Fire Mode
7
0-52
In90
Digital Input status: for troubleshooting (dependent upon NO/NC contact)
0
0-1
Output Terminal Group
Ouput selections are typically assignable for digital outputs OU31 thru OU35
OU1
AO1 assignment:
0
= Freq;
1
= Out Current:
2
= Out Volt;
3
= DC Bus;
4
= TQ;
5
= Pwr
0
0-15
OU7
AO2 assignment:
0
= Freq;
1
= Out Current:
2
= Out Volt;
3
= DC Bus;
4
= TQ;
5
= Pwr
0
0-15
OU31
Relay 1:
0
= None;
1
= FDT1;
5
= OL;
7
= Under Load;
9
= Stall;
10
= OV;
11
= UV
0
0~40
OU32
Relay 2:
0
= None;
1
= FDT1;
5
= OL;
7
= Under Load;
9
= Stall;
10
= OV;
11
= UV
0
0~40
OU33
Q1 Open Collector Output Define:
0
= None;
14
= Run;
22
= Ready
14
0~40
OU34
Relay 3:
0
= None;
1
= FDT1;
5
= OL;
7
= Under Load;
9
= Stall;
10
= OV;
11
= UV
0
0~40
OU35
Relay 4:
0
= None;
1
= FDT1;
5
= OL;
7
= Under Load;
9
= Stall;
10
= OV;
11
= UV
0
0~40
OU41
Digital Output status: troubleshoot:
0
= None;
1
= FDT-1;
2
= FDT2;
3
= FDT3;
4
= FDT4
0
00-11 bit
Cm
Communication Group
AP
Application Group
AP1
App Mode:
0
= None;
1
= Reserved;
2
= Process PID
0
0 -2
AP16
PID Output
0.00
PID
AP17
PID Reference Value
0.00
PID
AP18
PID Feedback Value
0.00
PID
AP19
PID Reference Setpoint
50.00
%
AP20
PID Reference Source:
0
= Keypad;
1
= V1;
3
= V2;
4
= I2;
5
= Int 485
0
0-15
AP21
PID F/B Source:
0
= V1;
2
= V2;
3
= I2;
4
= Int 485;
0
0-14
AP22
PID P-Gain
50.0
%
AP23
PID I-Time
10 sec
0 - 200.0 sec
AP29
PID Limit Hi
60.00 Hz
-/+ 300.00 Hz
AP30
PID Limit Low
-60.00 Hz
-/+ 300.00 Hz
AP37
PID Sleep detection time in seconds
60.0
Sec
AP38
PID Sleep frequency in Hz
0.00
Hz
AP39
PID Wake-up level in %
35
%
Protection Group
Pr4
Load Duty:
0
= Normal Duty ;
1
= Heavy Duty
1
0-1
Pr5
Input/output open phase protection: Bit low =
Off
; Bit High =
ON
(see manual)
0
0-1
Pr6
Open-phase input voltage band: adjustable (see manual)
40
1-100V
Pr8
Auto Restart:
0
= No;
1
= Yes
0
0-1
Pr 9
Retry Number
0
0-10
Pr10
Auto Restart time in seconds
0.0
0-60
Pr20
Overload Trip Select:
0
= None;
1
= Free-Run;
2
= Decel
0
0-2
Pr21
Overload Trip Level
180
30-200%
Pr22
Overload Trip Time
60 sec
0-60 sec
Pr90
Warning Information
Pr91
Fault history 1 - nOn = None or No fault recorded
Pr92
Fault history 2
Pr93
Fault history 3
Pr94
Fault history 4
Pr95
Fault history 5
Pr96
Fault history deletion:
0
= No;
1
= Yes (clears recorded faults in Pr91 - Pr95)
0
0~1
Note: Shaded areas above denote most frequently used parameters
WD4X Quick Start Guide
Common Drive Setup Parameters
(continued)