Copyright 2020 WorldWide Electric Corporation
The Globe icon is a registered trademark of WorldWide Electric Corporation
Document No: WD4X - QSG - 072020
1-800-808-2131
11
Group
Name
Description
See drive manual for complete configuration capabilities
Default
Value
Value
Range
New
Value
Operation Group (use ˄ or ˅ arrows keys) best to begin from Hz displayed
0.00
Frequency speed reference on keypad (0.00 before a new value is entered)
0.00
Min/Max
ACC
Accel Time in seconds
20.0
0-600.0
dEC
Decel Time in seconds
30.0
0-600.0
dru
Command Source:
0
= Keypad;
1
= FX/RX1;
2
= FX/RX2;
3
= Int 485;
4
= Field bus
1
0-5
FX/RX are hardwire terminal blocks for external switch connections
Frq
Frequency Setting Method:
0
= Keypad1;
2
= V1;
4
= V2;
5
= I2;
6
= Int485;
8
= FldBus
0
0-16
drC
Forward or Reverse control:
F
= Forward ;
r
= Reverse
F
F-r
dr
Drive Group (use ˂ or ˃ arrows keys) best to begin from Hz displayed
dr09
Control Mode:
0
= V/F;
2
= Slip Comp;
4
= IM Sensorless;
6
= PM Sensorless
0
0-6
dr14
Motor HP size
.5-30
dr15
Torque Boost:
0
= Manual ;
1
= Auto 1;
2
= Auto 2
0
dr18
Base Frequency:
60.00
30-400 Hz
dr19
Start frequency
0.50
0-10.00 Hz
dr20
Maximum frequency: Range of 40.00 to 400.00 Hz
60.00
40-400.00 Hz
dr21
Hz/RPM Select:
0
= Hz Display and
1
= RPM Display
0
0-1
dr85
Parameter Read
dr86
Parameter Write
dr89
Changed Parameters:
0
= No;
1
= Yes
dr90
ESC Key functions:
0
= Return;
1
= JOG;
2
= Local / Remote
2
0-2
dr92
Parameter Save:
0
= No ;
1
= Yes
0
0-1
dr93
Parameter initialize:
0
= No;
1
= All Grp;
2
= Dr;
3
= bA;
4
= Ad;
5
= Cn;
6
= In;
7
= OU
0
0-16
Factory default controlled by dr93
XX
Basic Group
ba4
Command Aux Src:
0
= Keypad;
1
= Rx/Rx-1;
2
= Fx/Rx 2;
3
= Int 485
1
0-4
ba5
Freq 2nd Source:
0
= Keypad 1;
2
= V1 ;
4
= V2;
5
= I2;
9
= Int 485
0
0-16
bA7
V/F Pattern:
0
= Linear;
1
= Square;
2
= User V/F;
3
= Square 2
0
0-3
bA9
Time scale for Ramp:
0
= 0.01 sec ;
1
= 0.1 sec ;
2
= 1 sec
0
0-2
bA10
Base frequency:
0
= 60 Hz ;
1
= 50 Hz (input power freq)
0
60/50 Hz
bA11
Motor pole number (total poles - NOT pole pairs)
4
2~48
bA13
Motor nameplate Full Load Amps
bA14
Motor No Load Current in Amps (typical value of 20-40% of FLA)
bA15
Motor rated voltage: VFD model specific
230/460V
bA19
VFD input power voltage
230/460V
bA20
Auto tuning:
0
= None;
1
= All Rotation;
2
= All Static;
3
= Rotate Lsigma;
6
= Static
0
0~6
Ad
Advanced Group
Ad1
Acc Pattern:
0
= Linear and
1
= S-Curve
0
0-1
Ad2
Decel Pattern:
0
= Linear and
1
= S-Curve
0
0-1
Ad8
Stop mode:
0
= Decel;
1
= DC Brake;
2
= Free Run;
3
= Resv;
4
= Power braking
0
0-4
Ad9
Run Prevent:
0
= None;
1
= FWD Prevent;
2
= REV Prevent
0
0-2
Ad24
Frequency limit:
0
= No and
1
= Yes
0
0-1
Ad25
Frequency low limit: 0.0 to high limit
0.50
0-400 Hz
Ad26
Frequency high limit: minimum frequency to maximum frequency
60.00
0.1-400 Hz
Ad64
Cooling fan control:
0
= During Run;
1
= Always On;
2
= Temp Control
0
0-2
Ad74
Regen Avoidance Select:
0
= NO ;
1
= YES
0
0-1
Ad75
Regen Avoidance Level: DC bus voltage level
700
300-800
240v AC Line (range 335-350vDC) or 480v AC Line (range 690-715vDC)
Ad76
Comp Frequency Limit: usually good to set at 60.00 Hz Max
1.00
0-60.00 Hz
Ad77
Regen Avoidance P Gain: Range of 0.0 to 100.0%
50
0.0-100.0%
Ad78
Regen Avoidance I Gain: Range of 20 to 30,000 mili-seconds
500
20-30000ms
Ad80
Fire Mode Select:
0
= None;
1
= Fire Mode;
2
= Fire Mode Test
0
0-2
Note: Shaded areas above denote most frequently used parameters
WD4X Quick Start Guide
Common Drive Setup Parameters