Connect Power In-Feed to Power Module
Snap color coded Power In-Feed
Cable to Power Module
Connecting Power In-Feed to Building Power
Note: This step should only be performed by a professional
licensed electrician.
Based on the National Electric Code (NEC) Article 220-14,
receptacle outlets shall be calculated at 180 VA per duplex.
Workrite electrical products are rated for use in 120 V systems
which yield a duplex rating of 1.5 A. Because most applications
actual circuit usage is variable or unknown, we recommend
using a max circuit rating of 80% as a guide to determine
how many receptacles should be connected per circuit. This
translates into 8 duplex or 16 simplex outlets on a 15 AMP
circuit and 10 duplex or 20 simplex outlets on a 20 AMP circuit.
Some local codes may vary from the NEC code therefore these
are only recommendations and local codes should always be
checked and followed.
WARNING!
Always install the Power In Feed as the last step when assembling a Benching System Power Module System.
Power connection for power entry options offered with this daisy chain power system must be connected by
a commercial electrician.
Do not electrically connect to more than one source of power supply.
Always verify the electrical system is connected to one and only one source of power supply.
WIRING SCHEMATIC
4 wire 2 circuit: 2 Hots, 1 Neutral, 1 Ground
2 utility circuits share a neutral and a ground
* The National Electric Code provides recommendations to the number of receptacles that can be
connected per circuit. ECA recommends using 75% loading per circuit as a guide; please consult
with your local inspector as codes may vary in different geographic locations
1-2-G
1-2-N
1H
2H
Green
White
Black
Red