Boiler/compartment clearances

Greenstar FS CDi 

ErP 

– 6720919078 (2015/12)

4.2

Airing cupboard clearances

The dimensions below show the minimum space required to install and service the boiler within an airing cupboard. 

If a compartment is built around the boiler after installation, then the compartment must be separated from the boiler space by a 
noncombustible partition as described in BS 6798.

4.3

Vented compartments

If the clearances available are less than those stated for an unventilated compartment or an airing cupboard then ventilation must 
be provided as described in BS 5440.

A minimum of two air vents of equal size must be fitted, one at low level and another at high level on the same wall or access door 
using the same air for circulation.

item

Minimum clearances (mm)

1

2300

2

625

3

600

4

200

5

25

1)

1) From the front of the boiler and the front of the shelf

6

100

7

100

1)

From the front of the boiler and the front of the shelf

6720818077-09.1W

o

1

#

Boiler

Air source

Vent area

1

30CDi

ErP

Internal room or 
space

 310cm

2

42CDi

ErP

440cm

2

2

30CDi

ErP

Outside

 155cm

2

42CDi

ErP

 

220cm

2

3

All

100mm space between the 
boiler and vents

6720818077-10.1W

o

2

1

3

Summary of Contents for Greenstar FS 30CDi ErP

Page 1: ...EALED OR OPEN VENT CENTRAL HEATING SYSTEMS 6 720 818 078 2015 12 The appliances are for use with Natural Gas or L P G Cat II 2H3P type C13 C33 C53 C93 Natural Gas FS 30CDi ErP Regular GC number 41 406...

Page 2: ...y efficient offering you economical running costs and value for money It sits in SEDBUK 2005 Band A scoring highly in SEDBUK 2009 and is therefore among the top energy rated boilers available There is...

Page 3: ...ved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision Combustible and Corrosive Materials Chemically aggressive substances can...

Page 4: ...etedbytheinstalleratthetimeofinstallation Itconfirms that the boiler hasbeen installed and commissioned according to the manufacturer s instructions The logbook provides space for the recording of reg...

Page 5: ...oiler controls Boiler Controls 1 Master switch for ON OFF 6 Not used 2 Power ON and fault indicator blue 7 Central heating temperature control 3 Boiler display 8 Service Engineer button only 4 Reset b...

Page 6: ...0 Fig 3 Settings for the central heating temperature with approximate temperatures 3 2 1 Controlling the central heating Central heating systems must be controlled effectively using a programmer or ti...

Page 7: ...protection Leave master switch on 1 Turn the central heating temperature control 7 to frost protection 3 3 1 Frost protection for the heating system If remote pipe work is likely to be subject to free...

Page 8: ...ndicator 2 will stop flashing The boiler will function normally dependent on programmer and room thermostat settings 6720808851 05 1Wo 1 2 3 4 5 6 max reset eco 3 2 4 If the fault cannot be cleared by...

Page 9: ...ce with the addition of cupboards shelves etc next to the boiler item Minimum distance requirements for compartments 1 Overall height of compartment 2 Overall depth of compartment 3 Overall width of c...

Page 10: ...unventilated compartment or an airing cupboard then ventilation must be provided as described in BS 5440 A minimum of two air vents of equal size must be fitted one at low level and another at high l...

Page 11: ...yed then it will be necessary to contact the Worcester Bosch Group This table gives information on basic operating system problems Problem Cause Remedy EA fault code flashing on display No gas supply...

Page 12: ...up Appointments Team see back cover for details Contact your installer in order to find a permanent solution to the problem When calling Worcester Bosch Group you may be asked for the error code This...

Page 13: ...which our products are sold to ensure optimum recycling All of our packaging materials are environmentally compatible and can be recycled 9 Tips on energy saving Heating economically The boiler provid...

Page 14: ...f this boiler is fitted to a sealed system and water leaks are found or if excessive bleeding is required then a service engineer must be contacted to inspect the installation and rectify any fault On...

Page 15: ...ed by faulty installation neglect misuse or accidental damage or the non observance of the instructions contained in the Installation and Users Instructions leaflets viii that the appliance has been u...

Page 16: ...9 SPARES 0330 123 9779 LITERATURE 0330 123 9119 TRAINING 0330 123 0166 SALES 0330 123 9669 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Tel 0330 123 9559 Worcester Bosch Group is a bra...

Reviews: