should be fitted as shown in Fig. 6,6a.
Insert the bayonet end of the filling key into the corresponding cutouts
in the filling loop housing and twist to lock the key in place.
Turn the grey knob anti-clockwise to allow water ingress and fill until
the pressure gauge reads 2.5 bar.
Turn the grey knob clockwise to stop filling and remove the filling key
by lining up the bayonet end of the key with the cutouts in the filling
loop housing and withdrawing the key.
N.B. The key must always be removed from the filling loop housing
after the system has been filled to prevent accidental filling and to
comply with Byelaw 14 of the Water Byelaws Scheme.
Store the key in a safe place for future use and refit the bottom panel.
The automatic air vent will vent the appliance. Check that the air vent
cap has been loosened. See Fig. 18.
Check that the pressure relief valve operates by turning the knob anti-
clockwise until it releases. Water should be expelled from the discharge
pipe. See Fig. 27.
Lower the facia panel to gain access. Refer to Section 15.3, c.
Set the Expansion Vessel Pressure
The charge pressure of the expansion vessel as dispatched is 0.5 bar,
which is equivalent to a static head of 5 metres (17 ft). The charge
pressure must not be less than the static head at the point of
connection. A Schraeder type tyre valve is fitted to the expansion vessel
to allow the charge pressure to be increased if necessary.
Set the system pressure
Release water from the system using the relief valve test knob (see Fig.
27), until the system design pressure is obtained, up to a maximum of
1.5 bar.
Initial system design pressure (bar) = Expansion vessel charge pressure
+ 0.3 bar.
NOTE:
1 bar is equivalent to 10.2 metres (33.5ft) of water.
Set the movable pointer on the pressure gauge to coincide with the
indicating pointer giving a permanent record of the set system
pressure.
If the pressure indicated on the pressure gauge is greater than 2.6 bar
when operating at the maximum central heating temperature, an extra
expansion vessel must be fitted to the system as close as possible to
the appliance central heating return connection.
The appliance (as dispatched) can accommodate a system volume of
about 83 litres. Refer to BS 7074 Part 1. If the system volume is in excess
of that accommodated by the expansion vessel fitted to the appliance
then an extra vessel must be fitted as close as possible to the central
heating return connection of the appliance.
Any extra vessel fitted must be pressurised to the same figure as the
integral vessel. If the expansion vessel fails then the specified
replacement must be fitted.
13.3 PROGRAMMER
Any programmer fitted on the appliance should be set up at this stage
following the instructions sent with the programmer.
The programmer will retain the settings for up to three weeks following
an interruption in the electricity supply.
13.4 APPLIANCE OPERATION
Turn off the gas and electricity supplies to the appliance.
Loosen the burner pressure test point screw on the gas valve and
connect a pressure gauge. See Fig. 28.
Undo the two screws and hinge down the facia to gain access to the
mode switch. Refer to Fig. 12.
Domestic Hot Water.
Set the gas valve mode switch, at the rear of the facia, to the maximum
position. Refer to Fig. 26.
Turn on the gas and electricity supplies.
Set the CH temperature control knob fully anti-clockwise to
and the DHW temperature to MAX.
Open a hot water tap.
A continuous ignition spark will occur until the burner is alight and
18
Fig. 27. Pressure relief valve.
Turn knob
anti-clockwise
to test
Pressure
relief
valve
Fig. 28. Gas Valve
Max
2mm
Allen key
Min
3mm
Allen key
Gas valve
sealing
cap
Burner
pressure
test point
Electrical
connections
modulator
(Blue:Blue)
Minimum / Maximum pressure
adjuster -
rotate Allen key clockwise to
increase and anti-clockwise to
decrease the pressure.
Inlet
pressure
test point
Main gas
valve
connections
Gas valve
bracket
Summary of Contents for 24CDi
Page 28: ...28 109 ...