Woodward
Manual XRI1-ER
36
TD_XRI1-ER_12.03, Rev. C
8.4 Output relays
Contacts:
2 relays with 2 changeover contacts;
3 relays with 1 changeover contact
The output relays have with the following characteristics:
maximum breaking capacity
250 V AC / 1500 VA / continuous current 6 A
for DC voltage:
ohmic
L/R = 40 ms
L/R = 70 ms
300 V DC
0.3 A/90 W
0.2 A/63 W
0.18 A/54 W
250 V DC
0.4 A/100 W
0.3 A/70 W
0.15 A/40 W
110 V DC
0.5 A/55 W
0.4 A/40 W
0.2 A/22 W
60 V DC
0.7 A/42 W
0.5 A/30 W
0.3 A/17 W
24 V DC
6 A/144 W
4.2 A/100 W
2.5 A/60 W
Max. rated making current:
64 A (VDE 0435/0972 and IEC 65/VDE 0860/8.86)
Making current:
max. 20 A (16 ms)
mechanical life span:
30 x 10
6
operating cycles
electrical life span:
2 x 10
5
operating cycles at 220 V AC / 6 A
Contact material:
silver cadmium oxide (AgCdO)
8.5 Power supply
Auxiliary voltage
16 - 360 V DC/16 - 250 V AC
Power consumption:
standby 3 W operating 5 W
The connection terminals are C9, E9.
Max. allowed interruption of the
auxiliary supply without effecting
the function of the device:
50 ms
Propper connection of the terminal
is essential for the EMC withstand of the relay.
Use wires of min. 1.5 mm
2
.
8.6 Inputs, Blockage and Reset
Low-range:
For rated voltages
24 V, 48 V, 60 V
U
ON
≥ 10 V
U
OFF
≥ 8 V
Current consumption
1 mA DC at 24 V
High-range:
For rated voltages
100 V, 110 V, 125 V, 220 V, 230 V
U
ON
≥ 70 V
U
OFF
≤ 60 V
Current consumption
1.5 mA DC at 360 V DC or 11.0 mA AC at 230 V DC
Technical data subject to change without notice!