Load Sharing Module
Manual 02035
8
Woodward
The other end of the shields must be left open and insulated from any other
conductor. Do not run shielded signal wires with other wires carrying large
currents. See Application Note 50532,
EMI Control for Electronic Governing
Systems
, for more information.
Where shielded cable is required, cut the cable to the desired length and prepare
the cable as instructed below and shown in Figure 2-1.
Figure 2-1. Preparation of Shielded Cables
1. Strip outer insulation from both ends, exposing the braided or spiral wrapped
shield. Do not cut the shield on the end nearest to the Load Sharing Module.
Cut off the shield on the end away from the unit.
2. Use a sharp, pointed tool to carefully spread the strands of the shield.
3. Pull the inner conductors out of the shield. Twist braided shields to prevent
fraying.
4. Connect lugs to the shield and to the control wires. Number 6 slotted or
round crimp-on terminals are used for most installations. Connect the wires
to the appropriate terminals on the module.
Installations with severe electromagnetic interference (EMI) may require shielded
wire run in conduit, double shielded wire, or other precautions.