background image

VENT INSTALLATION 

INSTALLATION PLANNING 

There are two basic types of direct-vent installation:

• Horizontal Termination
• Vertical Termination

It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the 
wall thickness. 

FOR HORIZONTAL TERMINATION

Select the amount of vertical rise desired. All horizontal run of venting 
must have 

1

/

4

" rise for every 12" of run towards the termination. 

You may use up to three 90° elbows in this vent configuration. See 

Horizontal Termination Configurations

 on pages 19 and 20.

FOR VERTICAL TERMINATION

Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, 
and allow for sufficient vent height above the roof line. 

NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows. 
The appliance is approved for use with three 90° elbows maximum or a combination of 90° and 45° elbows up to a 
maximum of 270°. 

For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows 
will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See 

Installing Vent System in a Chase

 

below. If pipe is enclosed in chase, it is not exposed. 
It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. 
Certain limitations apply to vent configurations and must be strictly followed.

INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE

A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required for 
such venting. 

Never run the vent pipe level or downward. 
This may cause excessive temperatures which 
could cause a fire. 

WARNING

When installing in a chase, you should insulate the chase as you would the outside walls of 
your home. This is especially important in cold climates. Insulation should be considered 
a combustible material. Maintain proper clearances to all combustible materials. 

NOTICE 

Treatment  of  firestops  and  construction  of  the  chase  may  vary  from  building  type  to 
building type. These instructions are not substitutes for the requirements of local building 
codes. You must follow all local building codes.

NOTICE 

14

Summary of Contents for SANTA MONICA N-E

Page 1: ...ion adjustment alteration services or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE YOUNG CHILDREN SHOULD BE SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE CHILDREN AND ADULTS ...

Page 2: ...nation Configuration 19 Below Grade Installation 21 Vertical Through the Roof Installation 22 Installation for Vertical Termination 23 Cathedral Ceiling Installation 24 Fireplace Installation 25 Check Gas Type 25 Installing Gas Piping to Fireplace Burner Checking Gas Pressure 27 Electrical Installation 28 Electrical Wiring 28 Vent Installation 12 Gas Connection 26 V Glass Frame Removal 29 Firebox ...

Page 3: ...tion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches diz ziness and or nausea If you have these signs the fireplace may not have been installed properly Get fresh air at once Have the fireplace inspected and serviced by a qualified service person Some people are more affected by carbon monoxide than others These include pre...

Page 4: ...the absence 15 This appliance when installed must be electrically rating plate etc in this fireplace Use only the gas type indicated on 14 Do not use any solid fuels wood coal paper cardboard 13 Never place anything on top of fireplace other objects 12 Do not use this fireplace to cook food or burn paper or 21 Young children should be carefully supervised when they are in the same room as the appl...

Page 5: ...r the Natural Fuel Gas Code ANSI Z223 1 of local codes with the National with local codes or in the absence The installation must conform The appliance is not approved forcloset or recessed installations TESTED TO ANSI Z21 88 2014 CSA 2 33 2014 CGA 2 17 M91 R2009 CSA P 4 1 09 STANDARDS Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe CODE APPRO...

Page 6: ...rround Material Noncombustible Measuring Tape Piping Complying with Local Codes Electric Drill and Bits Tee Joint Pliers Pipe Sealant Approved for use with Propane LPG Square Resistant to Sulfur Compounds Pipe Wrench I n the USA the appliance must be derated 4 for every 1 000 ft above 2 000 ft elevations at the factory Read this homeowner smanual thoroughly and follow all instructions carefully In...

Page 7: ...1 8 between covering material and fireplace to allow for metal fireplace front to expand and contract during operation any damages due to covering materials used If tiles are to be applied covering the fireplace face a layer of cement board must Do not fill spaces around firebox with insulation or other materials This could cause a fire be used as a substrate 5 PLEASE NOTE Natural stone products m...

Page 8: ...ace Dimensions 8 9 GAS AND ELECTRICAL ACCESS HOLES BOTH SIDES FIREPLACE DIMENSIONS SANTA MONICA 22 75 10 5 7 25 7 TOP VIEW 22 75 _ _ 16 22 33 25 ELBOW o 43 30 VENT 43 14 75 29 13 75 36 5 35 FRONT VIEW RIGHT SIDE VIEW WITH 30 DEGREE STARTING ELBOW ...

Page 9: ...bstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section found in this manual for allowable venting configurations These units can be installed in a bedroom or bathroom See National Fuel Gas Code ANSI Z233 1 NFPA 54 current edition the Uniform Mechanical Code current edition and Local Bui...

Page 10: ...de brackets are adjustable from 1 2 to 5 8 to accommodate different thickness of material SECURING FIREPLACE TO FLOOR OR FRAMING Figure 5 Securing Fireplace to Floor and Framing Studs Framing Screws Side adjustable bracket Screws Screws Side adjustable bracket Side adjustable bracket Side adjustable bracket _ _ _ _ _ _ _ _ ____ ____ _ _ _ _ ____ NOTE If installed in mobile home fireplace must be b...

Page 11: ... the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING The fireplace face may be completely covered with any non combustible ma terial Allow clearance for removal of front air panel 6 6 6 6 6 6 6 14 minimum 6 90 minimum Minimum 7 from both side walls 12 maximum depth COMBUSTIBLE MANTEL and glass door Make sure that...

Page 12: ...ion other than permitted by these instructions FINISHING MATERIAL NOTE Any remote wiring i e remote control wall switch and optional fan must be done prior to final finishing to avoid costly reconstruction INSTALLATION INFORMATION VENT INSTALLATION Never obstruct or modify the air inlet or outlet This may create a fire hazard WARNING Read all instructions completely and thoroughly before attemptin...

Page 13: ...use common vent systems WARNING A Minimum of 4 Clearance to the Top Is Required Along Horizontal Length of Pipe until Flue Pipe Goes Through Nearest Wall WARNING Horizontal sections of this vent system require a minimum clearance of 4 from the top of the pipe and 1 minimum to the sides and bottom Vertical sections of this system require a minimum of 1 clearance to combustible materials on all side...

Page 14: ...loor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installing Vent System in a Chase below If pipe is enclosed in chase it is not exposed It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust Ce...

Page 15: ... air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved driveway located on public property 7 2133mm minimum M Clearance under veranda porch deck or balcony 12 305mm minimum N Clearance above a roof shall extend a minimum of 24 610mm above the highest point when it passes through the roof surface a...

Page 16: ...e to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the horizontal run to the face of the Example If the vertical dimension from the floor of the unit is 7 2 14m the horizontal run to the face of the outer Sidewall Vent Graph showing the relationship between ver...

Page 17: ...ed See Figure 13 1 6 6 Maximum H x 9 W wall and frame as shown See Figure 12 229 229 for noncombustible material such as masonry block or concrete a 7 229mm X 229mm rectangle hole H x 9 3 Attach vent pipe assembly to the fireplace Set fire place in front of its permanent location to insure minimum clearances Mark the wall for a 9 vent pipe end Be sure to allow for 1 2 190mm diameter hole is accept...

Page 18: ... 15 5 Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination The pipe overlap should be a minimum of 11 4 Apply silicone to the outer pipe connection Fasten all vent connections with screws provided 7 Slide the wal...

Page 19: ... up with the sid ing It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace or the top of the Transition Elbow to the face of the outer wall The Commonwealth of Massachusetts requires the installation and USE of Carbon Monoxide detectors in...

Page 20: ...tal run the length of the horizontal run MUST be reduced by 18 45cm This does not apply if the 45 elbows are installed on the vertical part of the vent system The maximum number of elbow degrees in a system is 270 See Figure 22 Figure 21 Maximum Vent Run with Elbows Figure 20 Horizontal Run Reduction Figure 22 Maximum Elbow Usage 90 90 Elbow 3 1 2 3 1 2 3 4 7 6 10 B HORIZONTAL TERMINATION CONFIGUR...

Page 21: ...aving a clearance of approximately 4 below snorkel See Figure 21 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant caulking supplied around the 4 and 7 snorkel collars 6 Slide the snorkel into the vent pipes and secure to the wall 7 Level the soil so as to maintain a 4 clearance below snorkel See Figure 23 Figure ...

Page 22: ... in the system is 270 See Figure 26 The minimum height of the vent above the high est point of penetration through the roof is 2 610mm 40 Maximum Height 8 Minimum Height 40 Maximum Height 8 Minimum Height 10 Maximum 10 Maximum 1 2 3 4 1 2 3 4 Support Straps Every 3 Support Straps Every 3 Elbow 2 45 Total Angular Variation 270 Support Straps Every 5 Vertical Restrictor Disk Restrictor Disk Restrict...

Page 23: ...onnections are fully twist locked See Figure 13 page 17 Figure 27 Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45 Elbows Ceiling Firstop Figure 28 If area above is a room install firestop above framed hole as shown Figure 29 If area above is not a room install firestop below framed hole as shown Continued on next page Firestop Nails Nails Firestop FLAT CEILING INSTALLATION 1 Cut a...

Page 24: ...Ceiling Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Cathedral ceiling installations can be very tricky 1 Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box Mark the outline of the cathedral ceiling support...

Page 25: ...regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 32 Pointing the vent down protects it from freezing rain or sleet External Regulator 100 lb min Propane LP Supply Tank Ve...

Page 26: ...ps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure 33 Gas Connection Tee Joint Pipe Nipple Cap Approved Flexible Gas Line CSA Design Certified Equipment Shutoff Valve with 1 8 NPT Tap Sediment Trap Drip Leg Natural Gas From Gas Meter 5 W C to 10 5 W C ...

Page 27: ...ontrol Control Shaft Control Knob Switch Bracket Blower Plug In Duplex Outlet Located underneath firebox floor against Blower Location Side View Strips Exhaust Port Screw Green Ground Wire Spade Terminals Lower Firebox Cavity FRONT BACK see page 5 BLOWER FAN LOCATION Outlet Pressure Tap Pilot Adjustment Inlet Pressure Tap lower right outside wall as shown on page 5 Velcro 2 The appliance and its a...

Page 28: ...on and Canadian Electrical Code CSA C22 1 WARNING Label all wires before disconnecting when servicing controls Wiring errors can cause improper and dangerous operation CAUTION This fireplace requires 110V AC electrical supply for normal operation in order to power up blower and 7V DC adapter which is required to operate Remote Control However during power outage situation its electronic system DFC...

Page 29: ...OTE Avoid contacting the glass to any 29 SAFETY SCREEN AND GLASS DOOR REMOVAL Continued on the Next Page Front air panel Left side panel Right side panel Glass door with weld on top bracket and Washers Nuts Springs spring washer nut stud surface and be careful to not damage ...

Page 30: ...ding the Safety Screen in upper position if necessary by lifting up and moving out to the center STEP 2 Remove the left and right side panels STEP 3 Lift and remove the Safety Screen STEP 4 Locate 3 three 1 4 nuts holding springs on top of the glass frame Using a 7 16 ratchet remove all three nuts and then springs and washers from the studs SAFETY SCREEN AND GLASS DOOR REMOVAL 30 ...

Page 31: ...HE STUD IS EXPOSED SAFETY SCREEN AND GLASS DOOR REMOVAL 31 WARNING If there is broken glass wear protective gloves to carefully remove from the appliance DO NOT OPERATE THE APPLIANCE ofthelowerchannel andremovebyanglingthe framedownto the left STEP5 Carefullylifttheglassdoorassemblyout ...

Page 32: ...acket and Glass Frame out from the fireplace 2 Fill the tray with glass media supplied Do not place media on burner or block air flow between burner and tray as shown 3 Place Log 1 behind the burner as shown 4 Place Log 2 next to Log 1 as shown Do NOT place the log directly on the pilot assembly 5 Place Log 3 in front of the burner as shown Continue on next page 32 ...

Page 33: ... next to Log 3 as shown Safety screen both side panels and Front Air panel If any scratches occur on painted surfaces they can be touched up 9 Place Log 6 next to Log 5 as shown 10 Double check that neither pilot nor burner ports are blocked with the logs or glass media Replace the Glass frame with light coat of high temperature spray paint STOVE BRIGHT 1990 Satin Black can be ordered from Woodbri...

Page 34: ...or this appliance Any safety screen guard or barrier removed for servicing the appliance must be replaced prior to operating the appliance STEP 1 Remove front air panel and both side panels STEP 2 Angle the safety screen as shown on the picture and carefully bring into the fireplace opening STEP 3 Position the safety screen inside of the fireplace in front of the glass door Locate the two small ve...

Page 35: ...tabs in the panel with the slots in the face and slide downward Make sure the side panel is secured properly Repeat Steps 5 and 6 for the Left Side Panel STEP 7 Angle the Air Front Panel beneath the bottom of the screen Support the Air panel on the left and right Side Panels STEP 8 Tilt the Panel down to rest on the face support 35 ...

Page 36: ...ss panel close access panel Open access panel See counterclockwise 10 Turn on all electric power to the appliance See REMOTE Close access panel the Remote Control OPERATING INSTRUCTIONS 36 in Owner s Manual ...

Page 37: ...d insert into the battery bay as indicated on the battery covel 2 Place the 3 posilion slider switch in the REMOTE position 3 Insert the end of a paper clip into the hole marked PRG on the receiver front cover The receiver will beep three times to indicate that it is ready to syn chronize with a transmitter 4 Install the 3AAA batteries in the transmitter battery bay located on the base of the tran...

Page 38: ...he set temperature is now displayed see Figure 32 2 Adjust the set temperature by pressing the up or down arrow keys until the desired set temperature is displayed on the LCD screen see Figure 32 Room Temperature Set Temperature Figure 30 Remote Control Display in Farenheit and Celsius board will open the main valve outlet and the main burner will ignite A single beep from the receiver will confir...

Page 39: ...o beep will sound from the receiver when a transmitter command is sent Replace batteries when this happens Transmitter The life span of the transmitter batteries depends upon various factors battery quality number of appliance ig nitions number of thermostat set point changes etc When the transmitter batteries arc low an icon will appeal on the LCD display see Figure 4a Replace batteries when this...

Page 40: ... be ordered from the manufacturer Do not use substitute materials Clean the ceramic glass periodically Condensation will some times form on the glass during a cold startup This is normal for all gas fireplaces and inserts This condensation often attracts dust and lint to the surface of the glass The initial paint curing of the appliance can also leave a slight film on the glass This is a temporary...

Page 41: ...used Replace any glass that is chipped cracked or broken Replacement glass door assemblies MUST be supplied by the fireplace Never operate the fireplace if the glass is broken Never operate the fireplace without the glass door properly secured Keep children and pets a safe distance away NEVER use abrasive materials Do not remove the glass when hot Allow glass to cool before removal When cleaning t...

Page 42: ...ion Cap 46DVA HC 2 1 High Wind Vertical Termination 46DVA VCH 3 6 6 Pipe Length 46DVA 06 3 6 9 Pipe Length 46DVA 09 3 6 12 Pipe Length 46DVA 12 3 6 24 Pipe Length 46DVA 24 3 6 36 Pipe Length 46DVA 36 3 6 48 Pipe Length 46DVA 48 4 6 11 To 14 5 8 Pipe Adjustable 0911 4 6 17 To 24 Pipe Adjustable 0917 5 6 45 Elbow 46DVA 45 6 6 90 Elbow 46DVA 90 7 6 Flashing 0 12 To 6 12 Roof Pitch 46DVA F6 8 6 Storm ...

Page 43: ...ILLUSTRATED PARTS LISTS continued CONTROL COMPARTMENT BURNER COMPARTMENT FIREBOX COMPONENTS 2 3 4 5 6 14 1 7 13 8 10 11 12 15 15 16 17 18 19 21 23 24 25 9 FIREPLACE COMPONENTS 18 22 20 21 26 43 ...

Page 44: ...CPI IPI MODE 120 Vac INPUT 7 Vdc STABILIZED SUPPLY OUTPUT MOTOR IPI CPI RECEIVER DC SUPPLY SPLIT FLOW ON OFF TPTH TH DFC SUPPLY DC SUPPLY GROUND 885 PROFLAME Orange Green Chassis connection Remote control GTM This diagram shows replaceable SIT Proflame parts used in your fireplace 11 25 24 23 1 5 6 26 44 ...

Page 45: ...OL DFC BOARD 1 7 A100010 A100010 THERMOSTAT BLOWER WITH SPEED CONTROL 1 8 D200020 D200020 VALVE BRACKET 1 10 W100071 W100071 BURNER 1 11 C200003 C200004 PILOT ASSEMBLY 1 12 D100019 D100019 PILOT BRACKET 1 13 F200100 F200100 3 8 NPT X 5 16 COMPRESSION CONNECTOR 1 9 D300015 D300016 ORIFICE 1 14 F200064 F200064 3 8 NPT X 3 8 FLARE CONNECTION 1 15 I100015 I100015 FIREBOX GASKET 1 16 D100059 D100059 ME...

Page 46: ...n chamber Ensure that the glass is properly secure and latch Frequent pilot outage A Pilot flame may be too high or A Clean and adjust the pilot flame for maximum flame impingement The pilot and main A Inner vent pipe leaking exhaust A Check for flue product leak Replace defective pipe section Flame burn blue and A Insufficient oxygen being supplied A Ensure that the vent cap is installed properly...

Page 47: ...0 Elbows Quantity 45 Elbows ALTITUDE Feet Above Sea Level Was Stove Derated Yes No If Yes To What Orifice Size Unusual Structure Near Vent Inside Corner Trees Shrubs Other Termination Please Describe Prevalent Wind Conditions Other Installation Notes The installer should complete the form below that describes the details of the installation Having this written record of installation information av...

Page 48: ... neglect misuse abuse alterations negligence of others including the installation thereof by unqualified installers 2 the costs of removal reinstallation or transportation of defective parts on the appliance or 3 incidental or consequential damage All service work must be performed by an authorized service representative This warranty is expressly in lieu of other warranties express or implied inc...

Reviews: