VENT INSTALLATION
Figure 7 - Combustible Clearances for Vent Pipe
This fireplace must be vented to the outside. The venting system must NEVER be attached
to a chimney serving a separate solid fuel burning appliance. Each gas appliance must
use a separate vent system. Do not use common vent systems.
WARNING
A Minimum of
4
" Clearance to the Top Is
Required Along Horizontal Length of Pipe until
Flue Pipe Goes Through Nearest Wall.
WARNING
Horizontal sections of this vent system require
a minimum clearance of
4
" from the top of
the pipe and 1" minimum to the sides and
bottom. Vertical sections of this system require
a minimum of 1" clearance to combustible
materials on all sides of the pipe.
WARNING
1" Clearance Is Acceptable
at the Outside Wall.
4
��
��
"
13