11
9660 & 11260 Fire Deck Coal-Fired Oven
Installation and Operation Manual
INSTALLATION CLEARANCES
1-inch clearance to combustible
construction on all sides�
WARNING: DO NOT PACK THE AIRSPACE
BETWEEN THE ENCLOSURE AND THE OVEN
WITH INSULATION OR OTHER MATERIAL.
Combustible construction
Non-combustible construction
14-inch top clearance to combustible
construction
1-inch side clearance to combustible
construction
Install only on a non-combustible floor surface
which extends 36 inches in front of, and 30 inches
to either side of the doorway opening
Any facade construction 6 inches to either
side of the doorway opening and above
must be non-combustible
Front
view
Plan
view
An ongoing program of product improvement may require us to change
specifications without notice.
FD-9660-CL, FD-11260-CL,
Revised November 2015. Doc no: M0044.03
or visit
woodstone-corp.com
Wood Stone Corporation
1801 W. Bakerview Rd.
Bellingham, WA 98226 USA
Toll Free 800.988.8103
Tel 360.650.1111
Fax 360.650.1166
1.
The Wood Stone Fire Deck 9660 and Fire Deck 11260 ovens must have a minimum 1-inch clearance to combustibles from
all sides, and 14-inch clearance to combustibles from the top (see figures below)� Any construction 6 inches to either side
of the doorway and above must be non-combustible� If building a facade that will contact the oven, use completely non-
combustible materials
*
� Please note that standard Drywall (or Sheetrock) is considered a combustible� If sealing an opening
between the enclosure and the oven, use non-combustible building materials�
2.
Install this oven on a non-combustible floor surface which extends at least 36 inches in front, and 30 inches to either side of,
the doorway opening�
3.
Any combustibles within 3 feet of the oven doorway should be protected in a manner acceptable to the authority having
jurisdiction�
*
When non-combustible building materials contact the body of the oven, the respective clearances are transferred to those
non-combustibles�
!
WARNING:
Do not pack required air space (clearance) with insulation or other materials. When non-
combustible building materials contact the body of the oven, the clearances to combustibles are
transferred to those non-combustibles.