Operation
Electrical Requirements (US Version Only)
Operation
MHdoc012819
2-12
2
CAUTION!
The resaw motors and the transformer are
prewired for 480 V, 60 Hz power supplies. If you plan to use
a 480 V, 60 Hz mill with another type of power supply, you
will need to rewire the motor to avoid damage to the
machine.
The electrical requirements for the resaw are listed below.
IMPORTANT!
The resaw is
wired for use with a 480 volt power supply. To operate the resaw with 240V or 380-415V
power supplies, a transformer is required. Refer to the table below:
See Table 2-2.
See Table 2-3.
The machine FLA required for the resaw is listed below.
The operator’s positions and E-STOP locations are shown in the figures below.
Conversion From/To
240 to 480 volts
380-415 to 480 volts
No. of Heads
2
4
6
2
4
6
Mfg. Part No.
EE30T3118H EE45T3065H EE75T3065H EE30T2611H EE45T2611H EE75T2611H
AWMV Part No.
069712
069711
068057
069616
068054
068055
TABLE 2-2
Motor
HP
Power Supply
Machine FLA/# of Heads
Volts
PH
Hz
2
4
6
25
240
1
1
Transformer Required. FLAs include a transformer.
3
50/60
125
188
313
380-415
3
50
75
113
188
480
3
60
50
95
140
TABLE 2-3