background image

18

LT 90 Owners Manual

2015

If the alarm LED is on, an alarm has taken place

To see the kind of alarm, the max (min) reached temperature and

alarm duration do as follows:

1.   Push the Up or Down key.

2.   On the display the following message is shown:

 

“HAL”

 for high temperature alarm (

“LAL”

 for the minimum

  alarm), followed by the

 Maximum (minimum) temperature.

 Then the 

“tiM”

 (

tiM

e) message is displayed, followed by the

 

“Duration”

 in h.mm.

3.   Then  the  instrument  displays  the  temperature  once  again.

NOTE1:

 if an alarm is still occurring the “tim” shows the partial

duration.

NOTE2:

 the alarm is recorded when the temperature comes back

to normal values.

 

1.   Hold the SET key pressed for more than 3s, while the recorded

  alarm  is  displayed.  (The  rSt  message  will  be  displayed)

2.   To  confirm  the  operation,  the  “rSt”  message  starts  blinking

  and the normal temperature will be displayed.

  

  Push and immediately release the 

SET

 key: the

  

  display  will  show  the  Set  point  value;

  Push  and  immediately  release  the 

SET

  key  or  wait  for  5

  seconds to display the probe value again.

1.   Push the 

SET

 key for more than 2 seconds to change the Set

  point value;

2.   The value of the set point will be displayed and the “˚C” or 

  “˚F” starts blinking;

3.  To change the Set value push the    or    arrows within 10s.

4.  To memorise the new set point value push the 

SET

 key again

  or wait 10s.

To change the parameter’s value operate as follows:

1.  Enter the Programming mode by pressing Set and     keys       

  for three seconds. (the “˚C” or”˚F” LED start blinking)

2.   Select the required parameter. Press the 

SET

” key to display 

  its value.

3.   Use “

UP

” or “

DOWN

” to change its value.

4.  Press “

SET

” to store the new value and move to the following

  parameter.

To exit:

 Press 

SET + UP

 or wait 15s without pressing a key.

NOTE:

 the set value is stored even when the procedure is exited

by waiting the time-out to expire.

1.  Keep pressed for more than 3 s the     and     keys.

2.  The “

POF

” message will be displayed and the keyboard will 

  be locked. At this point it will be possible only to see the set 

  point or the MAX o Min temperature stored.

3. If a key is pressed more than 3s the “POF” message will be

  displayed.

5.1  HOW TO SEE THE ALARM DURATION AND MAX 

(MIN) TEMPERATURE  

5.2  HOW TO RESET A RECORDED ALARM OR ONE 

THAT IS STILL OCCURRING 

6.  MAIN FUNCTIONS 

6.1  HOW TO SEE THE SETPOINT 

 

6.2  HOW TO CHANGE THE SETPOINT 

6.3  HOW TO CHANGE A PARAMETER VALUE 

6.4  HOW TO LOCK THE KEYBOARD 

6.5  TO UNLOCK THE KEYBOARD 

7.  PARAMETERS 

REGULATION 

DISPLAY 

ALARM 

8.  ALARM SIGNALS 

Message 

Cause 

Outputs 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

8.1  ALARM RECOVERY  

9.  DEFAULT SETTING VALUES  

Label 

Name 

Range 

°F  Level

Set 

 

1

r

P

0

7

1

 

S

U

÷

S

L

 t

n

i

o

p

 t

e

S

Hy 

Differential 

0,1

25.5°C/ 1

 255°F 10 

Pr1 

ALL 

Minimum temperature 

alarm 

-50.0°C

Set/-58°F

Set 120

Pr1 

Keep  pressed  together  for  more  than  3s  the    and    keys,  till

the 

“Pon”

 message will be displayed.

Hy Differential:

 (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for

  set point. Fan Cut IN is Set Point Minus Differential (Hy). Fan

  Cut  OUT  is  when  the  temperature  reaches  the  set  point.

CF Temperature measurement unit:

 

°C

=Celsius; 

°F

=Fahrenheit. 

WARNING

: When the measurement

  unit is changed the SET point and the values of the parameters

  Hy,  LS,  US,  Ot,  ALU  and  ALL  have  to  be  checked  and

   modified if necessary).

rES Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal

  point display.

dLy Display Delay:

 (0 ÷20.0m; risul. 10s) when the temperature

  increases, the display is updateed of 1°C/1°F after this time.

ALL Minimum temperature alarm:

 (-50.0 ÷ SET°C; 58÷230°F 

  when this temperature is reached the alarm is enabled and 

  fan will shut off.

AFH Differential for alarm recovery:

 ((1÷45 °F) It sets the value

  above the alarm value for alarm recovery.

Probe alarm “

P1

” starts some seconds after the fault in the related

probe; it automatically stops some seconds after the probe restarts

normal operation. Check connections before replacing the probe.

Temperature alarms “

HA

” and “

LA

” automatically stop as soon as

the  thermostat  temperature  returns  to  normal  values.

Alarms  “

EA

”  and  “

CA

”  (with  i1F=bAL)  recover  as  soon  as  the

digital input is disabled.

Alarm “

CA

” (with i1F=PAL) recovers only by 

switching off and on

the instrument.

E.T.C. Guide

Reference

Summary of Contents for LT 90

Page 1: ...oor Wood Fired Hydronic HEater LT 90 LT SERIES OWNERS MANUAL Retain this manual Northwest Manufacturing Inc 600 Polk Ave SW Red Lake Falls MN 56750 www woodmaster com 800 932 3629 Manual PN 7994 590 Rev 3 1 ...

Page 2: ...hooting 24 Warranty 25 28 Specifications 29 Notes 30 31 Thank you for purchasing a quality wood furnace from WoodMaster This product was designed to de liver easy trouble free operation for years to come Check out other WoodMaster heating products at www woodmaster com or our line of quality pellet grills at www woodmasterpelletgrills com Table of Contents ...

Page 3: ...m Only responsible adults should operate your LT 90 If the LT 90 is not fired properly damage could result and the warranty may be voided Never allow children to play near or tamper with the Furnace fuels or any other part of the system Always keep the area around and in front of the system clean and free from combustible materials Keep animals away from the system The operation may not be continu...

Page 4: ...er can supply the genuine service parts and install them All fuels must conform to certain quality standards to ensure trouble free operation of the furnace Use of unapproved fuels may result in faulty operation and a voided warranty Never use the following trash household garbage plastics gasoline rubber naphtha leaves and materials treated with petroleum prod ucts ie particleboard railroad ties ...

Page 5: ...el Door Stainless Steel Chim ney Vent Cap E T C Panel Maintenance Schedule Serial Model Numbers Primary Return Cold Water Temp Snap Disc Thermistor Probe Primary Supply Hot Drain Draft Inducer Heat Exchanger Clean Out Secondary Return Cold Solenoid Combustion Fan Secondary Supply Hot Features ...

Page 6: ...cturing Inc A draft inducer may be used to ensure proper draft under all conditions Note Remove the chimney cap prior to lighting the furnace CAUTION Using a non insulated chim ney or failure to use a Class A Insulated Chimney WILL result in a voided Warranty When using more than four feet of chimney extension external support is needed Pad Supports The LT 90 should be placed on cement blocks The ...

Page 7: ...e buried two to three feet deep If lines travel through a low or wet area they should be insulated and installed in a water tight piping PVC Note Leave a minimum of three feet of water line exposed above ground at the furnace to insure adequate length for connection Note Before insulating and burying the water lines label the hot water supply line at both ends Once the lines are covered you will b...

Page 8: ...e pump Then attach the hot water supply 1 Pex Water Line 0020 130 to the fitting using 1 Pex Crimp Ring 0020 145 Water Return Attach the 1 Pex x 1 MIP 0020 140 fitting to the Water Return Valve Then attach the cold water return 1 Pex Wa ter Line 0020 130 to the fitting using 1 Pex Crimp Ring 0020 145 Wiring The Pump Remove the cover on the pump Then using an approved wire connect the ground wire t...

Page 9: ...be enters the bottom fitting of the heat exchanger and exits the top fitting which returns to the furnace If the plenum is too large or too small it must be altered to fit the heat exchanger properly Note The water to air heat exchanger must be in stalled below any existing off peak electric coils already in the plenum After the installation of the WoodMaster add on water to air exchanger the air ...

Page 10: ...ater Return to WoodMaster Existing Heat Zone Return WoodMaster Water to Water Heat Transfer Unit Circulating Pump for Existing Hot Water Heating System Existing Hot Water Boiler Cold Water Return from Heat Exchanger Domestic Water Supply for filling boiler Cold Water Return to WoodMaster Filling With Water Connect a garden hose between a domestic water supply and the furnace fill valve 0020 325 wh...

Page 11: ...als fall out of the furnace when opening the fuel door During periods of warmer weather you may find it to have creosote inside the firebox It is important to fill the furnace only with enough wood to last up to a 12 hour period After burning your furnace for a period of time you will discover how much wood is needed per day and what types of wood burn the best Loading the Furnace When loading you...

Page 12: ...ts smallest usable form To make sure that you are rotating your ashes properly follow the instructions below 1 With your Ash Hoe pull the ash from the back of the furnace to the front and level coal bed 2 Load wood length wise towards the back Be careful not to damage rear door or plug air holes Remove ash from the front of the furnace as needed Make sure not to remove any hot coals with the ash a...

Page 13: ...2 seconds the draft will open and the draft fan will turn on The display will continue to flash LA and the water temperature will be displayed until the water temperature reaches 140 F ALL 20 After water temperature reaches 140 F only the water temperature will be displayed until the water temperature falls to 120 F Note The fan switch must be in the on position Note Fan switch can be shut off whe...

Page 14: ...y and quick reference The instrument shall not be used for purposes different from those described hereunder It cannot be used as a safety device Check the application limits before proceeding Some parameters such as CH are not applicable to Woodmaster see default settings grid fig 15 on next page Check the supply voltage is correct before connecting the instrument Do not expose to water or moistu...

Page 15: ...ed and the keyboard will be locked At this point it will be possible only to see the set point or the MAX o Min temperature stored 3 If a key is pressed more than 3s the POF message will be displayed 5 1 HOW TO SEE THE ALARM DURATION AND MAX MIN TEMPERATURE 5 2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS STILL OCCURRING 6 MAIN FUNCTIONS 6 1 HOW TO SEE THE SETPOINT 6 2 HOW TO CHANGE THE SETPOINT 6...

Page 16: ...temperature reading Changing the All 1 When the E T C reads ALL from the previous step press the set button The number that appears is the Low Alarm temperature 2 To adjust the number press the up or down arrow 3 Press the Set button to lock in the setting Definitions Set Point The temperature at which the fan will shut down Hy aka Differential The amount in degrees the temperature has to drop in ...

Page 17: ... limits before proceeding Some parameters such as CH are not applicable to Woodmaster see Section 9 Default Settings Check the supply voltage is correct before connecting the instrument Do not expose to water or moisture use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation Warning disconnect all ...

Page 18: ...only to see the set point or the MAX o Min temperature stored 3 If a key is pressed more than 3s the POF message will be displayed 5 1 HOW TO SEE THE ALARM DURATION AND MAX MIN TEMPERATURE 5 2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS STILL OCCURRING 6 MAIN FUNCTIONS 6 1 HOW TO SEE THE SETPOINT 6 2 HOW TO CHANGE THE SETPOINT 6 3 HOW TO CHANGE A PARAMETER VALUE 6 4 HOW TO LOCK THE KEYBOARD 6 5 T...

Page 19: ...r down arrow 3 Press the Set button to lock in the setting Definitions Set Point The temperature at which the fan will shut down until hysteresis is achieved Hy aka Differential The amount in degrees the temperature has to drop in order to start the fan ALL aka Low Alarm The temperature at which the furnace will shut down At which point the furnace should be reloaded and the control is reset Note ...

Page 20: ...and furnace may be hot Ash Removal and Disposal Weekly or as needed Remove the ashes when the furnace is very low on wood Use a shovel to take the ashes from the front of the fire box and use a Ash Hoe to pull the ashes from the rear of the furnace to create a level bed of hot coals The ashes should be placed in a metal container with a tight fitting lid The closed container of ashes should be pla...

Page 21: ...when not in use will void your warranty When the furnace is in use be sure that you maintain a good ash rotation This should be done weekly If you are using a spark arrester or a chimney cap you will need to provide your furnace with a little more maintenance It is very important that you keep these areas free of any creosote build up at all times Failure to do this will cause harm to the roof of ...

Page 22: ...22 LT 90 Owners Manual 2015 Wiring ...

Page 23: ...23 LT 90 Owners Manual 2015 Wiring ...

Page 24: ...th wood being burned Wood or system need to be addressed If Furnace Boils 1 Check fire door Be sure door was not left open 2 Check fire door rope This is the fire resistant gasket around the Fuel Door Make sure the door has a tight seal 3 Check air intake on fire door Make sure cover closes tight 4 In extremely warm weather a smaller amount of wood should be used 5 Check Auger Tube Plug for air le...

Page 25: ...ents including but not limited to the outer shell paint insulation doors and latches during normal usage for a period of one 1 years from the date of installation START OF WARRANTY PERIODS The Warranty Period shall begin on the date the Furnace installation has been completed the Original Date of Installation In the event of dispute as to the Date of Original Installation the shipping date of your...

Page 26: ...ace Failure to send in a water sample annually will void the warranty Boiler treatment must be used Freeze protection must be guaranteed at all times III This Warranty is non transferable and only covers the Original Owner at the original site of installation IV Northwest Manufacturing Inc shall have the time needed and unobstructed access to the Furnace for the purpose of conduct ing tests of the...

Page 27: ...Cut here and mail registration card Northwest Manufacturing Inc 600 Polk Ave SW Red Lake Falls MN 56750 Northwest Manufacturing Inc 600 Polk Ave SW Red Lake Falls MN 56750 PLACE POSTAGE HERE ...

Page 28: ... Date of Purchase Dealers Name Address City State Zip Phone Serial Number How did you learn about our product Radio Newspaper Internet TV Print Other Would you like information on other products from Northwest Manufacturing Inc Yes No I have read the owners manual and understand the proper usage of my WoodMaster LT 90 Signature Printed Name Fold Fold Fold Fold Fold Fold Fold Fold Fold Fold Fold Fo...

Page 29: ...ications Power Connection Single Phase 120v 60 Hz Maximum Current Draw 7 Amps 120 v 60 Hz Draft Fan Max Draw 1 Amp 120 v 60 Hz Maximum Power Output 90 000 BTU Weight 1800 Pounds approx Water Jacket Capacity 120 Gallons Door Size 16 x16 ...

Page 30: ...30 LT 90 Owners Manual 2015 Notes ...

Page 31: ...31 LT 90 Owners Manual 2015 Notes ...

Page 32: ...Northwest Manufacturing Inc 600 Polk Ave SW Red Lake Falls MN 56750 www woodmaster com 800 932 3629 Manual PN 7994 590 ...

Reviews: