6
LT 90 Owners Manual
2015
Choosing Location
When installing your WoodMaster, keep in mind the direction of the winds during heating months. Try to place
the furnace in an area where exhaust will not be a problem for yourself or any surrounding neighbors.
LOCATION: It is recommended that the unit be located with due consideration to the prevailing wind direction.
• When using more that 4 feet of chimney extension external support is needed.
• Should be located greater than 100 feet from any residence not served.
• If located between 100 and 300 feet to any residence not served, it is recommended that the
stack be at least 100% of the height of the peak of the residence, plus an additional 2 feet.
Always remember to comply with all applicable state and local codes.
Chimney Specifications
To insure proper insulation, use only a Class A Insulated Chimney and Chimney Adapter from your local Wood
-
Master Dealer or Northwest Manufacturing, Inc. A draft inducer may be used to ensure proper draft under all
conditions.
Note: Remove the chimney cap prior to lighting the furnace.
CAUTION: Using a non-insulated chim
-
ney or failure to use a Class A Insulated Chimney WILL result in a voided Warranty. When using more than
four feet of chimney extension external support is needed.
Pad Supports
The LT 90 should be placed on cement
blocks. The blocks should be at least 6”
wide, 10” long and 3” thick. Two feet of
clearance from the front and rear of the fur
-
nace and at least one foot clearance on the
sides is recommended. Failure to install the
WoodMaster LT 90 on a proper support will
result in a voided warranty. Never use com
-
bustable materials, such as wood blocks,
to support the LT 90. A full cement pad is
recommended if the supporting ground is
soft, sandy, or othewise unable to support
the furnace on the pads alone.
Residence not
served by furnace
2 feet
Residence
served by furnace
Minimum of 100 feet
Chimney height
should be 2 feet above roof line
60.00
96.00
54.00
6.00
6.00
16.00
16.00
12.00
12.00
11.50
48.00
14.00
14.00
F
F
F
F
SUP
SUP
RET
RET
Installation