- 9 -
10. Technical data
Typ
SR 200.R10/1
Temperature range
+5...+ 40°C
Temperature seback
2 ... 10K, adjustable
Temperature sensor
NTC (internal)
or
KTY (remote, please order
separately
Tolerance of sensor
±1K
Operating differential
±0.1...±3.0K, adjustable
Proportional band
1...10K, adjustable
Width of pulse
1...15min, adjustable
Temperature resolution
Nominal
value
0.5K,
actual
value 0.1K
Nominal temperature setting
rotary knobs
Programme positions
16
Timer
Electronic 7-day timer
Battery storage reserve
1
approx. 15 minutes
Visual indication
LC-display
Operating voltage
230V AC (±10%)
Power consumption
approx. 2 VA
Relay contact
1 floating double-throw contact
Maximum permissible current
230V AC (± 10 %)
Electrical connections
screw terminals
Electrical lifetime
0.5 x 10
5
switching operations
Max permissible ambient
temperature 0...+
50°C
Storage temperature
-10...+70°C
Enclosure: Material
plastic
Protective kind
IP 20
Protective class
II in accordance with
DIN EN 60335-1
Dimensions
132 x 82 x 32mm (W x H x D)
Mounting
Wall mounting or on flush box
Cable entry
for surface wiring or rendering
Weight
approx. 250 grams
1
The battery storage reserve only refers to time.
Any other parameter remain stored fixed.
11. Wiring diagram
Subject to modification