Dimensions in parentheses are in
millimeters unless otherwise specified.
Planning Information
Pro 27"
(686)
Deep Wall Ventilation Hood
M O D E L P W 5 4 2 7 1 8 ( R )
Ducting for Pro 27" (686)
deep wall hoods.
30"
TO
36"
(762–914)
COUNTERTOP
TO BOTTOM OF
VENTILATION HOOD
18"
(457)
HEIGHT OF HOOD
WALL HOOD
DUCTWORK INSTALLATION
THROUGH ROOF
36"
(914)
STANDARD
FLOOR TO
COUNTERTOP
HEIGHT
27"
(686)
DEPTH OF HOOD
10"
(254) ROUND DUCT
SOFFIT OR CABINET
OR DUCT COVER
NOTE: HORIZONTAL DISCHARGE REQUIRES AN ACCESSORY KIT.
TRANSITION
22
1
/
4
"W x 9"D TO 10" ROUND
10"H (INCLUDING FLANGES)
ROOF CAP OR REMOTE BLOWER
VERTICAL DISCHARGE
D U C T I N G C O N S I D E R A T I O N S
Wolf Pro 27" (686) deep wall hoods are shipped
without the blower assembly. Internal, in-line
and remote blower assemblies are available.
IMPORTANT NOTE:
Install this ventilation hood
only with a Wolf blower.
Pro 27" (686) deep wall hoods have a vertical
discharge. A horizontal discharge kit is available
as a sales accessory.
The hood will operate most efficiently when
ductwork does not exceed 50' (15 m) in length.
Local building codes may require the use of
make-up air. Consult your local HVAC profes-
sional for specific requirements in your area.
IMPORTANT NOTE:
Wolf Pro 27" (686) deep
wall hoods must be vented to the outside. Use
only metal ductwork.
Refer to the illustration below for ducting
considerations for Pro 27" (686) deep wall
hoods.