![Wolf CWL-2-400 Installation And Operating Instructions Manual Download Page 50](http://html1.mh-extra.com/html/wolf/cwl-2-400/cwl-2-400_installation-and-operating-instructions-manual_992186050.webp)
Step
No
Description
Factory settings
Setting range
Comment
10.2 minimum voltage
input 1
0V
0V / 10V
Connector X-12
10.3 maximum voltage
input 1
10V
0V / 10V
10.4 Mode input 2
Off
On / Off
10.5 minimum voltage
input 2
0V
0V / 10V
Connector X-13
10.6 maximum voltage
input 2
10V
0V / 10V
11
Geo-heat exchanger
11.1 Switching on and off
Off
On / Off
11.2 Switch temperature 1
5 °C
0.0 °C / 10.0 °C
11.3 Switch temperature 2
25 °C
15.0°C / 40.0 °C
11.4 Mode valve 24 volt control
Closed
Open / Closed
11.5 Valve control
Relay output 1
Relay output 1/
Relay output 2/
Analogue output 1/
Analogue output 2
Setting values
xxxx
50 | WOLF GmbH
7100833_202010