Step
No
Description
Factory settings
Setting range
Comment
4.3
Filter reset
No
Yes / No
5
External heater
5.1
Preheater on and off
Off
On / Off
5.2
Postheater on and off
Off
On / Off
5.3
Temperature postheater
21 °C
15 °C / 30 °C
6
CO
2
sensor
6.1
Switching eBus CO
2
sensor off
and on
Off
On / Off
6.2
Min. PPM eBus CO
2
sensor 1 400 PPM
400 - 2000 PPM
6.3
Max. PPM eBus CO
2
sensor 1 1200 PPM
6.4
Min. PPM eBus CO
2
sensor 2 400 PPM
6.5
Max. PPM eBus CO
2
sensor 2 1200 PPM
6.6
Min. PPM eBus CO
2
sensor 3 400 PPM
6.7
Max. PPM eBus CO
2
sensor 3 1200 PPM
6.8
Min. PPM eBus CO
2
sensor 4 400 PPM
6.9
Max. PPM eBus CO
2
sensor 4 1200 PPM
7
Humidity sensor
7.1
Switching humidity sensor on
and off
Off
On / Off
7.2
Sensitivity of humidity sensor
0
+2 = most sensitive
0 = basic setting
-2 = least sensitive
8
Cascade
8.1
Appliance setting
0 (Master)
0 / 9
(0=Master; 1 t/m 9 = Slave 1 t/m Slave
9)
12
Central h heat recovery
12.1 Status
Off
On / Off
14
Communication
14.1 Type of Bus connection
ModBus
Off / ModBus/ externalBus
14.2 Slave address
20
1 - 247
For Modbus
14.3 Baudrate
19k2
1200 / 2400 / 4800 / 9600 / 19k2 /
38k4 / 56k / 115k2
For Modbus
14.4 Parity
Even
No / Even / Odd
For Modbus
15
Appliance settings
Setting values
xxxx
7100833_202010