10
3064361_201811
Type
CRL-iH-1300
CRL-iH-2500
CRL-iH-3500
Unit layout
Single piece
Single piece
Three piece
Length L
mm
1525 / 1525*
1626 / 1626*
1626 / 1830*
Length L1
mm
-
-
508
Length L2 (rotor part)
mm
-
-
610 / 814*
Depth D (incl. locks)
mm
750
950
1155
Total height
mm
1309
1716
1716
Height H
mm
1017
1424
1424
Foot height
mm
170
170
170
Control unit height
mm
122
122
122
Duct connection dimensions,
horizontal air routing
mm
int. 612x409
Intl 815x612
Intl 1019x612
Weight
kg
266 / 266*
381 / 381*
470 / 490*
(130+210+130)
(130+230+130)*
Nominal flow rate
m³/h
1300 at 460 Pa (ext.)
2500 at 600 Pa (ext.)
3500 at 980 Pa (ext.)
* with boost damper
Type
CRL-iH-4800
CRL-iH-6200
CRL-iH-9000
Unit layout
Three piece
Three piece
Three piece
Length L
mm
1728
1932
2136
Length L1
mm
610
712
814
Length L2 (rotor part)
mm
508
508
508
Depth D (incl. locks)
mm
1360
1665
2070
Total height
mm
1716
1716
1919
Height H
mm
1424
1424
1627
Foot height
mm
170
170
170
Control unit height
mm
122
122
122
Duct connection dimensions,
horizontal air routing
mm
intl 1222 x 612
intl 1527 x 612
intl 1934 x 714
Weight
kg
590
(180+230+180)
715
(220+275+220)
845
(275+295+275)
Nominal flow rate
m³/h
4800 at 450Pa (ext.)
6200 at 680Pa (ext.)
9000 at 1000Pa (ext.)
1 Outdoor air
2 Exhaust air
3 Supply air
4 Extract air
2
4
1
3
L2*
TWHE with boost
damper
L1
L2
L1
H
Total
H
T
L
170
122
5 CRL-iH unit layout
Summary of Contents for CRL evo max Series
Page 25: ...25 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 26: ...26 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 27: ...27 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 28: ...28 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 29: ...29 3064361_201811 13 Assembly CRL evo max 4x A1 ...
Page 30: ...30 3064361_201811 13 Assembly CRL evo max 4x 4x B1 B1 A1 ...
Page 31: ...31 3064361_201811 13 Assembly CRL evo max ...
Page 51: ...51 3064361_201811 21 Notes ...