Fans
Note
Use tools to tightly seal the doors before commissioning (unit tightness),
otherwise there is a risk of motor overload.
Carry out air flow rate tests with the doors closed.
Route test hose connections out of the unit (see flow rate calculation).
Changes are made via the BMK programming unit (see relevant operating
instructions).
Where the system is not commissioned by WOLF, check all inputs and outputs
for correct wiring and function.
- Frost protection function
- Fan rotational direction
- Outdoor air/extract air damper rotational direction
- Plausible sensor values (room sensor, supply air sensor, extract air sensor,
outdoor air sensor)
- Check motor currents
- Motor protection (thermal cut-outs / thermistors)
- Air flow monitoring
- Filter monitor
- Actuator, heating / cooling
- Heating circuit pump / cooling circuit pump
- As well as all other system-specific functions
The WOLF warranty will be void if the function test is not carried out
correctly.
Filter pre-dryer (accessory)
To prevent the electric heating coil from switching off, never operate the CRL
below its minimum air flow rate.
Follow the relevant safety regulations for electric heating coils.
The electric heating coil must be protected from moisture and water.
The filter pre-dryer starts automatically at outside temperatures below 5 °C.
Type
CRL
1300 2500 3500 4800 6200 9000
Recomm. Minimum air
volume
m³/h 600
1200 1800 2400 3100 4500
Type
CRL evo max
11000 13500 16500 19500
Recomm. Minimum air
volume
m³/h
5500
6500
8000
9500
17 Commissioning
Summary of Contents for CRL evo max Series
Page 25: ...25 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 26: ...26 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 27: ...27 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 28: ...28 3064361_201811 1 2 3 4 12 Unit splitting for handling purposes CRL ...
Page 29: ...29 3064361_201811 13 Assembly CRL evo max 4x A1 ...
Page 30: ...30 3064361_201811 13 Assembly CRL evo max 4x 4x B1 B1 A1 ...
Page 31: ...31 3064361_201811 13 Assembly CRL evo max ...
Page 51: ...51 3064361_201811 21 Notes ...