35
3064361_201710
16. Commissioning
Further settings for the
BMK and accessories
Further settings for the BMK programming unit can be found in the operating
instructions for the WRS-K control unit.
Accessories are installed in accordance with separate instruction manuals
which are provided with the relevant accessories.
CRL-6200 effective pressure
The fans used for the CRL-6200 have a k value of 188.
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
Δp
[Pa] 290 347 409 476 548 625 707 795 887 985 1088
V [m³/h] 3200 3500 3800 4100 4400 4700 5000 5300 5600 5900 6200
0
200
400
600
800
1000
1200
3000
3500
4000
4500
5000
5500
6000
V
= 188 x √
D
p
w
CRL-9000 effective pressure
The fans used for the CRL-9000 have a k value of 240.
Δp = effective pressure
(symbolic representation)
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
0
200
400
600
800
1000
1200
1400
3800
4600
5400
6200
7000
7800
8600
V
= 240 x √
D
p
w
Δp
[Pa] 278 352 434 525 625 734 851 977 1111 1254 1406
V [m³/h] 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000
Summary of Contents for CRL-A-1300
Page 21: ...21 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 22: ...22 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 23: ...23 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 24: ...24 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 41: ...41 3064361_201710 20 Notes...
Page 42: ...42 3064361_201710 20 Notes...
Page 43: ...43 3064361_201710 20 Notes...