15. Electrical connection
Electrical connection
The electrical connection may only be made by electricians in accordance with
local regulations.
When connecting the control unit and control accessories, observe the instructions
and wiring diagrams provided.
Once electrical connection work is complete, the installation must be subjected
to a safety test in accordance with VDE 0701-0702 and VDE 0700 part 500,
as otherwise there would be a risk of electric shock that could result in injury
or death.
Before working on the unit, shut it down via the isolator.
The control panel has cable entries for connecting the on-site cables.
Unit size
Basic devices
without
integrated
electric heating coil
Basic devices
with
integrated
electric heating coil
Power cable
on-site
fuse/MCB
protection
Power cable
on-site
fuse/MCB
protection
CRL-1300
3 x 1,5 mm²
16 A
5 x 1,5 mm²
10 A
CRL-2500
5 x 1,5 mm²
16 A
5 x 2,5 mm²
20 A
CRL-3500
5 x 2,5 mm²
20 A
5 x 6,0 mm²
35 A
CRL-4800
5 x 2,5 mm²
20 A
-
-
CRL-6200
5 x 4,0 mm²
25 A
-
-
CRL-9000
5 x 6,0 mm²
35 A
-
-
Even when the unit has been shut down, voltage will still be present at terminals
and connections of the EC fans. This means there is a risk of electric shock
that could result in injury or death.
Do not touch the EC fans for five minutes after disconnecting the power across
all poles.
Use a rubber mat if working on the unit when it is electrically charged.
Only use cables that meet local wiring regulations with regard to voltage, current,
insulation material, load etc. Always fit an earth conductor.
RCDs
Only AC/DC-sensitive fault current safety devices, type B, with 300 mA are
permissible. There is no personal safety protection if the unit is operated with
RCDs.
Regularly check the perfect function of all electrical equipment.
Observe the specified electrical fuse/MCB protection ratings.
We accept no liability for any damage or loss resulting from technical modifications
to WOLF control units.
Inlet for on-site
cables
Motor data
CRL-1300 CRL-2500 CRL-3500 CRL-4800 CRL-6200 CRL-9000
Rated voltage
1 x 230V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
3 x 400V
(50/60Hz)
Max. power consumption of both fans
1,0kW
2,1kW
5,0kW
3,4kW
6,0kW
11,0kW
Max. current draw of both fans
4,6A
3,2A
8,0A
5,2A
9,2A
17A
Drehzahl der Ventilatoren
3080 rpm
3400 rpm
2970 rpm
2600 rpm
2550 rpm
2200 rpm
IP rating / safety category
IP55 / Iso F IP55 / Iso F IP54 / Iso F IP54 / Iso F IP54 / Iso F IP54 / Iso F
Summary of Contents for CRL-A-1300
Page 21: ...21 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 22: ...22 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 23: ...23 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 24: ...24 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 41: ...41 3064361_201710 20 Notes...
Page 42: ...42 3064361_201710 20 Notes...
Page 43: ...43 3064361_201710 20 Notes...