16. Commissioning
Flow rate calculation
The flow rate is calculated using the effective pressure method. This involves
comparing the static pressure upstream of the inlet nozzle with the static
pressure in the inlet nozzle.
The flow rate can be calculated from the effective pressure Δp
w
(differential pressure of the two static pressures) using the following equation.
The doors must be closed to determine the correct flow rate. Route the test
hoses through the unit floor to the outside when conducting the test.
CRL-1300 effective pressure
Δp
[Pa]
43
62
85
111
140
173
209
249
293
V [m³/h] 500
600
700
800
900 1000 1100 1200 1300
The fans used for the CRL-1300 ave a k value of 76.
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
0
200
400
600
800
1000
1500
2000
2500
3000
3500
V
= 76 x √
D
p
w
CRL-2500 effective pressure
The fans used for the CRL-2500 ave a k value of 77.
Ef
fective pressure
Δp [Pa]
Flow rate [m³/h]
Δp = effective pressure
(symbolic representation)
0
200
400
600
800
1000
1200
700
1000 1300 1600 1900 2200 2500 2800
Δp
[Pa] 137
204
285
379
487
609
744
892 1054
V [m³/h] 900
1100 1300 1500 1700 1900 2100 2300 2500
V
= 77 x √
D
p
w
Summary of Contents for CRL-A-1300
Page 21: ...21 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 22: ...22 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 23: ...23 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 24: ...24 3064361_201710 1 2 3 4 12 Unit splitting for handling purposes...
Page 41: ...41 3064361_201710 20 Notes...
Page 42: ...42 3064361_201710 20 Notes...
Page 43: ...43 3064361_201710 20 Notes...