Commissioning
52 | WOLF GmbH 3066501_201910
6.7.2
Test the CO
2
levels with the casing open
► Remove the casing.
► Remove cap from right flue gas test port
(2)
.
► Select
parameter HG47
in the contractor level (BM-2) or the contractor menu (AM).
► Insert test probe approximately 70 mm.
Stage 1:
► Measure CO
2
content.
Table 6.1 Set value with casing open
.
HG
Casing open
CO
2
O
2
47
Stage 1
12.7 ± 0.3%
3.8 ± 0.4%
49
Stage 2
12.7 ± 0.3%
3.8 ± 0.4%
Table 6.1 Set value with casing open
CO
2
levels within set range:
►
Exit parameter HG47
.
► Select
parameter HG49
and repeat measurement.
► Exit
parameter HG49
.
CO
2
levels outside of set range:
► Exit
parameter HG49
.
► Set CO
2
level (
).
6.7.3
Setting CO
2
levels
► Select
parameter HG47
in the contractor level (BM-2) or the contractor menu (AM).
► Wait for approx. 2 minutes.
►
Select value
.
i
The CO
2
level can be increased by lowering the number or decreased by increasing the number.
► Adjust the number by ±1 in increments until the measured CO
2
level is within the set range.
► Exit
parameter HG47
.
►
Select parameter HG49
.
►
Select value
.
► Adjust the number by ±1 in increments until the measured CO
2
level is within the set range.
► Exit
parameter HG49
.
CO
2
cannot be configured properly within the setting limits:
► Check oil nozzle and air nozzle.
► Change the oil pump pressure (
6.7.4 Changing the oil pump pressure
i
If the heat generator fails to start with factory settings active, the parameters can be adjusted after
waiting for three minutes.