Planning
3066501_201910
WOLF GmbH | 23
Type Design variants
Maximum length [m]
1
COB-2
15
20
29
40
C53x
Connection to a flue in a shaft and supply air through
an external wall (room sealed, supply air pipe 4 m,
1x bend 87°)
DN 80/125
30
30
30
-
DN 110/160
-
-
-
30
C83x
Concentric connection to moisture-resistant flue gas
chimney and combustion air through external wall
(room sealed)
Calculation according to DIN
EN 13384 (balanced flue
chimney manufacturer)
C93x
Vertical flue for installation in a shaft, with minimum
dimensions rigid or flexible with horizontal concentric
connection pipe DN 60/110, vertical DN 60
Rigid DN 60
13
-
-
-
Flexible
DN 60
9
-
-
-
C93x
Vertical flue for installation in a shaft, with minimum
dimensions rigid or flexible with horizontal concentric
connection pipe DN 80/125, vertical DN 80 or DN 83
Rigid DN 80
29
24
21
-
Flexible
DN 83
27
21
17
-
C93x
Vertical flue for installation in a shaft, with minimum
dimensions rigid or flexible with horizontal concentric
connection pipe DN 110/160, vertical DN 110
Rigid DN 110
-
-
-
22
Flexible
DN 110
-
-
-
22
1
Available fan draught: COB-2-15: 32 - 65 Pa / COB-2-20: 45 - 65 Pa / COB-2-29: 55 - 105 Pa / COB-2-40: 70 - 150 Pa (maximum
length corresponds to the total length from the heat generator to the flue outlet)
Table 4.9
Permissible air/flue gas routing lengths [m]
Calculated length of air/flue gas bends
Bend
Type
Calculated length [m]
30°
Single wall
0.4
45°
Single wall
0.6
87°
Single wall
1.0
30°
Concentric
0.7
45°
Concentric
1.2
87°
Concentric
2.0
Table 4.10
Calculated lengths of air/flue gas bends
Calculation example
The calculated length of the air/flue gas routing system or standard flue is derived from the straight pipe
length and the length of any pipe bends.
Length of straight air/flue gas pipe = 5.5 m
87° support bend = 2.0 m
2 • 45° bend = 2 • 1.2 m
L = 5.5 m + 1 • 2.0 m + 2 • 1.2 m
L = 9.9 m