16
3061916_0611
Parameter
BM
Parameter
BM-Solar Explanation
Setting range
Factory
setting
min.
max.
SOL 01
P 01
Start differential solar cylinder 1
5 K
30 K
8 K
SOL 02
p 02
Stop differential solar cylinder 1
2 K
20 K
4 K
SOL 03
P 03
Collector cooling function
0 (OFF)
1 (ON)
0
SOL 04
P 04
Critical collector temperature
90 °C
150 °C
110 °C
SOL 05
P 05
Maximum collector temperature
100 °C
150 °C
130 °C
SOL 06
P 06
Maximum temperature, solar
cylinder 1
15 °C
90 °C
60 °C
SOL 07
P 07
Assignment, solar cylinder 1
0
8
0
SOL 08
P 08
Capturing the amount of heat
0 (OFF)
4
0
SOL 09
P 09
P 08
= 0 →
P 09
Not adjustable
P 08
= 1 →
Pulse value, pulse generator
P 08
= 2 →
Constant flow rate
P 08
= 3 or 4 →
Pulse value
external heat meter
0 l/pulse
0 l/min
-2
99.5 l/pulse
99.5 l/min
1
1 l/pulse
1 l/min
0
SOL 10
P 10
Glycol selection:
0 = Water
1 = Tyfocor L (Anro)
2 = Tyfocor LS (Anro LS)
3 = Propylene glycol
4 = Ethylene glycol
0
4
1
SOL 11
p 11
BUS feed
0
2
2
SOL 12
p 12
Configuration
1
14
1
SOL 13
p 13
Speed control, solar circuit pump 0 (OFF)
1 (ON)
0
SOL 14
p 14
Start differential solar cylinder 2
5 K
30 K
8 K
SOL 15
p 15
Stop differential solar cylinder 2
2 K
20 K
4 K
SOL 16
p 16
Maximum temperature, solar
cylinder 2
15 °C
90 °C
60 °C
SOL 17
p 17
Assignment, solar cylinder 2
0
8
8
SOL 18
p 18
Burner blocked during
return temperature raising
0 s
300 s
0 s
SOL 19
p 19
Start differential, return
temperature raising
4 K
30 K
10 K
SOL 20
p 20
Stop differential, return
temperature raising
2 K
20 K
5 K
SOL 21
p 21
Priority solar cylinder 1
0
2
0
SOL 22
p 22
Start differential
parallel cylinder operation
20 K
60 K
30 K
SOL 23
p 23
Differential temperature, bypass
8 K
50 K
15 K
SOL 24
p 24
Function output A4
0 (OFF)
3
0
SOL 25
p 25
Start temperature, thermostat
function
30 °C
90 °C
50 °C
SOL 26
p 26
Stop differential, thermostat
function 1/2
5 K
30 K
10 K
SOL 27
p 27
Tube collector function
0 (OFF)
2
0
SOL 28
p 28
Frost protection function
0 (OFF)
1 (ON)
0
Parameters used with SM2 solar module:
Parameter level