Subject to the solar module used, different parameters are available.
Parameters used with SM1 solar module:
Parameter
BM
Parameter
BM-Solar Explanation
Setting range
Factory
setting
min.
max.
SOL 01
P 01
Start differential solar cylinder
5 K
30 K
8 K
SOL 02
p 02
Stop differential solar cylinder
2 K
20 K
4 K
SOL 03
P 03
Collector cooling function
0 (OFF)
1 (ON)
0
SOL 04
P 04
Critical collector temperature
90 °C
150 °C
110 °C
SOL 05
P 05
Maximum collector temperature
100 °C
150 °C
130 °C
SOL 06
P 06
Maximum cylinder temperature,
solar cylinder
15 °C
90 °C
60 °C
SOL 07
P 07
Assignment, solar cylinder
0
8
0
SOL 08
P 08
Capturing the amount of heat
0 (OFF)
4
0
SOL 09
P 09
P 08
= 0 →
P 09
Not adjustable
P 08
= 1 →
Pulse value, pulse generator
P 08
= 2 →
Constant flow rate
P 08
= 3 or 4 →
Pulse value
external heat meter
0 l/pulse
0 l/min
-2
99.5 l/pulse
99.5 l/min
1
1 l/pulse
1 l/min
0
SOL 10
P 10
Glycol selection:
0 = Water
1 = Tyfocor L (Anro)
2 = Tyfocor LS (Anro LS)
3 = Propylene glycol
4 = Ethylene glycol
0
4
1
SOL 11
p 11
BUS feed
0
2
2
SOL 27 * p 27 *
Tube collector function
0 (OFF)
2
0
SOL 28 * p 28 *
Frost protection function
0 (OFF)
1 (ON)
0
SOL 33 * P 33 *
Hysteresis, solar cylinder
0.5 K
5 K
1 K
SOL 36 * P 36 *
Solar cylinder emergency
shutdown
60 °C
95 °C
95 °C
SOL 39 * P 39 *
Minimum collector limit
-25 °C
90 °C
10 °C
SOL 41 *
P 41 *
Function check, flow rate
0 (OFF)
1 (ON)
0
SOL 42 * P 42 *
Function check, gravity brake
0 (OFF)
60 °C
40 °C
SOL 44 * P 44 *
Reverse cooling function
0 (OFF)
1 (ON)
0
SOL 51 *
P 51 *
Proportion of glycol in water
P 10
= 0 →
P 51
Not adjustable
P 10
= 1 : Tyfocor L (Anro)
P 10
= 2 →
P 51
Not adjustable
P 10
= 3 →
P 51
Not adjustable
P 10
= 4 → Ethylene glycol
----
20 %
----
----
20 %
----
75 %
----
----
80 %
----
45 %
----
----
45 %
SOL 6O
p 60
Relay test
1
5
1
Parameter level
For function descriptions of the individual parameters, see the SM solar module instruction
manual.
* Parameters only effective from software version SM1/SM2 228_04.