
15
Installation instructions Gator
Rel. 1.2
8.2 Adjusting bus addresses lock
8.2.1 Gator 2000
• Bus address fix setted on 09.
8.2.2 Gator 3000/3010/5000
Position Coding switch
0
1
2
…
9
A
B
C
D
E
F
Bus address lock
00
01
02
…
09
10
11
12
13
14
8.2.3 Gator 6000/8000/9000
• Maximum 3 redundancy locks per system are available.
• Pairing of the address of the redundancy locks is mandatory according to table.
• The monitoring of the redundancy is only available with redundant laid bus cables and the input units Gator F/DF/R/DR .
• The monitoring of the redundancy is not active - activate configuration in Software GatorSelect and transmit via ibutton.
Lock 1
Lock 2
Lock 3
Position Coding switch
0
A
1
B
2
C
Bus address lock
00
01
02
8.3 Adjusting bus addresses input units Gator RO/FL/FS/F/DF/R/DR
• The input unit must be in full working order.
• The bus addresses of the input unit Bus address are factory-adjusted on 00.
• The address for the the input unit has to be unique in one system.
• Use the following key combination at the input unit: ***Address input unit ***
The address may have the value up 00, 01, 02 to 15 e. g. *** 02 ***
Bus address input unit
00
01
02
…
09
10
11
12
13
14
15
8 Bus address
• Within one system a maximum of 16 input units and a maximun of 15 locks can be connected.
• The address for the lock and the input unit has to be unique in one system.
• Gator 3000/3010/5000/6000/8000/9000: The bus addresses can be adjusted by turning the coding switch.
• Gator 6000/8000/9000: For redundancy you have to adjust 2 bus addresses for 1 lock.
8.1 Coding switch Gator 3000/3010/5000/6000/8000/9000
Coding switch