Shield Wire and outer surface is connected together, and Cable shield wire should be connected to Ground Terminal.
Ground Cable wire is AWG24, and in case of using Extension wire, the standard should be higher than Ground Wire standard.
In case of working on the terminal, to prevent the unwinding, use washer and to prevent the corrosion, use plated terminal and lug.
Ground point should be connected to rebar, floor, or Bus Bar.
(Ground Point should be considered with a local Industrial regulation, and Electric standards)
6. Ground Connection
1) Each Part Name
2) Working Principle
①
②
③
Pressure applied to the pressure input section, and the pressure value will convert into an electronical singal.
Measured pressure will be transferred after converting into 4 ~ 20 mA electrical current.
If requires zero adjustment, open the cap and turn with tool. (Zero trim : ±1.0 %)
5. Each Part Name and Working Principle
2 Wire Connection Socket
Pressure Input Section
Body
Zero Adjustment
07
English