1128500
WPC 2000 User Manual
2-8
Installation
Connecting AC Wiring
All wires can be run through flexible, liquid-tight conduit to the control as long as all circuits
are 115V. If your Top-stop circuits and Emergency-stop circuits are low voltage (for
example, 24V), run two conduits–one for 115V wires and one for 24V wires. Be sure to
number all wires so they are consistent with the electrical prints for your press.
Bring the wiring connections for AC power to a convenient point so that you can connect
them to the power terminal block at the top left of the enclosure (see Figure 2-5). No. 16 wire
(No. 14, if local codes require it) is recommended for these circuits with a minimum 75° C
temperature rating.
ELECTRIC SHOCK OR HAZARDOUS ENERGY
• Disconnect main power before installation.
• Remove all power to the press, press control, and other equipment used with the press.
• Remove all fuses and “tag out” per OSHA 1910.147 Control of Hazardous Energy (Lockout/
Tagout).
• Ensure that installation is performed by qualified personnel.
• Complete all installation procedures before connecting to the AC power source.
Failure to comply with these instructions will result in death or serious injury.
Figure 2-5. AC Input Wiring Connections
DANGER
!
LINE
NEUT
Connect ground wire
to set screw ground
terminal
Neutral
Line
Top left corner
inside enclosure
Input Power
Terminal block
Summary of Contents for wpc 2000
Page 91: ...1128500 WPC 2000 User Manual 2 64 Installation ...
Page 191: ...1128500 WPC 2000 User Manual 5 22 Troubleshooting ...
Page 209: ...1128500 WPC 2000 User Manual A 18 Extracts from OSHA and ANSI ...
Page 225: ...1128500 WPC 2000 User Manual G 6 Glossary ...
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......