5 Flue systems
To ensure safe and proper use, this air heater must be
connected to a flue system. This flue system must be
installed according to this manual as well as national and
local regulations. A flue system consists of a flue terminal,
piping and an optional condensate discharge system.
CAUTION!
Do not use flue terminals for condensing
appliances on non-condensing heaters. This can lead to
water inside the flue system.
NOTICE
Only use the prescribed flue material for the
roof terminal, wall terminal and for the piping between
the heater and the terminal. This is the only way the
installation will be approved.
NOTICE
Local regulations can require the flue terminal to
be placed at least 0,6 m above roof level.
NOTICE
Local regulations can require a minimum
distance between the flue terminal and air ventilation
openings on the building.
5.1 Flue terminals
The following flue terminals are compatible with this air
heater:
Model(s)
Vertical discharge
Flue terminal
Art. Nr.
XR10+
-
XR60+
DDV 80/125
IA8202*
* For h > 0,5m above the roof, use art.nr. IA8218
Model(s)
Horizontal discharge
Flue terminal
Art. Nr.
XR10+
-
XR60+
CT 80/125
IA8113
XR10+
-
XR60+
2-pipe terminal
GA8202
Figure 13 - Vertical flue terminal XR+
Figure 14 - Horizontal flue terminal XR+
5.1.1
Flue material
Only use CE marked flue material from the manufacturers
Muelink & Grol (M&G) and Burgerhout.