Instructions condensing Air heaters type XR version XR-GB-4001-a
Page 17/27
6.3 Start through the display in the heater
The manual test mode trough the display in the heater will only work for maximum 10 minutes.
1. Pres and hold the Return and – button for a few seconds. The display will show Lo / St
intermediate.
2. The heater will start up in Low fire.
3. Toggle between Low and High fire by pressing the + and – button,
4. Exit the service menu by pressing the – button until 0 is displayed.
5. The heater will always cool down the heat exchanger for a few minutes.
6. After 10 minutes the test mode will automatically end.
.
7
Adjusting the gas-control
In principle, it is
not
necessary to adjust the gas control after putting the unit into operation.
In case it needs to be adjusted, (e.g. after fitting a new one), this must be done only by a
qualified person.
Only use calibrated instruments!
A poor adjustment can lead to
overheating and / or production of toxic carbon monoxide!
The burner pressures can be adjusted as follows:
- Remove the cover from the gascontrol with the help of a (small) screwdriver.
-
Start the unit and first set the high burner pressure by turning screw (external 10mm).
The High / low coil must be energised !
-
De-energise coil (disconnect wire) and set low burner pressure by turning screw (slot for
screwdriver) Do not set lower than 3 mbar in order to avoid problems with inter-lightning of
burnerstrips.
TR10 up to 50
TR60 up to 125
Attention: Always check each burner pressure after any adjustment, as they influence each
other.