5
INSTRUCTION MANUAL
AIR HEATER TYPE DXA
3 Technical specifications
3.1 Performance
Technical specification
Unit
Type DXA v4.1
DXA75
DXA100
DXA120
Net nominal heat input
kW
75.0
99.8
120
Heat output
kW
75.0
99.8
120
Air output
m
3
/h
6000
6000
7000
Throw horizontal
m
40
40
45
Gas connection
G”
3/4"
3/4"
3/4"
Electrical connection (50 Hz)
V
230
230
230
Electrical power consumption
kW
0.55
0.55
0.8
Stand-by electrical power
consumption
kW
0.004
0.004
0.004
Electrical current (max.)
A
2.8
2.8
3.8
Protection class
-
IPX4D
Pressure switch point
mbar
15
15
15
Sound level (at 8 m)
dBA
79
79
81
Thermostat connection
-
2-wire low voltage communication bus or ON/OFF
Weight
kg
40
40
45
3.2 Gas types
3.2.1
Natural gas G20
Specification
Unit
Natural gas G20
Nominal supply pressure
mbar
20
Supply pressure (min. - max.)
mbar
17-25
Gas category
-
II
2
H
3
B/P
DE: II
2
ELL
3
B/P
BE: I
2
Er
FR: II
2
Er
3
B/P
NL: II
2
EK
3
B/P
Pressure switch point
mbar
15
Class
-
A3
Specification
Unit
DXA75
DXA100
DXA120
Gas consumption
m
3
/h
7.9
10.5
12.6
Burner injectors
n x Ømm
1x 8.5
1x 10.5
1x 12.0
Burner pressure
mbar
8.0
7.0
7.0
Summary of Contents for DXA100
Page 1: ...DXA en v2 0 12 2019 INSTALLATION MANUAL AIR HEATER TYPE DXA ...
Page 24: ......