3. How to see temperature set-point
1) Press and immediately release
SET
key, the display will show the set-point.
2) Press again and immediately release the
SET
key to display the probe value.
4. How to change the set-point
1) Press and hold the
SET
key until the “°C” or “°F” LED starts flashing and the
set-point is displayed.
2) Press
or
to change the set-point value within 10 sec.
3) Press the
SET
key again to store the new set-point value.
NOTE
: The unit turns on at set-point
Set
plus regulation differential
Hy
after anti-
short cycle
AC
has elapsed; the unit turns off at set-point
Set
.
5. How to start manual defrost
Press and hold
until defrost starts. The defrost indicator will be displayed.
6. How to activate quick cooling
Press and hold
until for more than 3 seconds. The compressor and liquid
line solenoid valve indicator will be displayed.
7. How to program parameters
1) Press and hold
SET
and
until the “
°C” or “°F”
LED starts flashing, then
release the keys.
2) Press and hold again the
SET
and
keys until the
Pr2
label is displayed, then
release the keys. The first parameter
Hy
will be displayed.
3) Press
or to scroll to the required parameter within 10 sec.
4) Press the “
SET
” key to display its value.
5) Use
or to change its value within 10 sec.
6) Press “
SET
” to store the new value and the display will flash 3 times.
7)
To exit
: Press
SET
and
or wait 15sec without pressing a key.
PARAMETER
DESCRIPTION
DEFAULT VALUE
Set
set-point (
°
)
55
Hy
temperature regulation
differential
(
°
)
4
AC
anti-short cycle delay (min)
10
Con
compress on with probe faulty
(min)
15
CoF
compress off with probe faulty
(min)
30
CF
temperature unit
(
°
F
/ °
C)
F: Fahrenheit
rES
display resolution
in: integer
dLy
temperature display delay (min)
1