32
Differential temperature
adjustment
Setting 16
Press “Mode” button to advance to Setting 16.
Press the “Up” or “Down” buttons to adjust to the
desired set point.
This setting changes the system/compressor. Turn on
temperature above set point. Factory default is set to
1°C.
Example: Sensor reading = 13°C
Setting 16 set to +1°C
System/compressor turns on at 14 Deg. C.
Deadband setting
Setting 17
Press “Mode” button to advance to Setting 17.
Press the “Up” or “Down” buttons to adjust to the
desired set point.
This setting is the minimal allowable temperature
difference between heating and cooling set points.
Maximum is 3°C, minimum is 1°C. Factory default is
set to 1°C
Test mode setting
Setting 18
Press “Mode” button to advance to Setting 7.
Press the “Up” or “Down” buttons to adjust to the
desired set point. When set to one (1) the
controller will automatically turn on all outputs
with the exception of electric heat. Factory default
is zero (0).
Zero (0) = Off
One (1) = On
System Selection
Setting 19
DO NOT CHANGE