26
Setting 11
Setting 11 is the defrost cut out temperature. This setting will be adjustable from 35°F to 50°F. Default
will be 40°F. There must be at least a 1°F difference between defrost cut in and cut out set points.
Note: This feature will be locked out for Wine Guardian.
Setting 12
Setting 12 is the compressor run time setting for defrost. It will be adjustable from 1 to 12 hours in 1
hour increments. Default will be 4 hours.
Note: This feature will be locked out for Wine Guardian.
Setting 13
Setting 13 is the room sensor calibration. This setting will allow the user to adjust the room tempera-
ture reading by +/-5°F. Default setting will be 0°F.
Setting 14
Setting 14 is the differential temperature adjustment. This setting will allow the user to adjust the turn on
differential from 1°F to 3°F (the turn off differential is fixed at 1°F). Default is 1°F.
Setting 15
Setting 15 is the deadband setting, which is the minimum allowable temperature difference between the
heating and cooling set points. This will be adjustable from 1°F to 5°F. Default is 2°F.
Setting 16
Setting 16 is the humidifier on/off feature. If set to off, the humidifier output and set point adjustment
will be disabled. If set to on, the user will be able to enter a humidity set point in the local user interface
and the humidifier output will energize based on that set point. The local user interface will always
display the RH% even if this feature is set to off.
Setting 17
Setting 17 is the fan auto/on feature. The user will have the option to set the fan operation to auto in
which case it will only turn on with a call for heating, cooling, or humidifier. They may also set the fan to
on which will run the fan continuously. The default setting will be auto.
Setting 18
Setting 18 is the test mode setting. When set to on, the control will automatically turn on all outputs with
the exception of electric heat. Default is off.
Setting 19
As factory set to Wine Guardian the set temperature range is 32°F -100°F with a default of 55°F, the
humidity set range is 10% - 90% with a default of 55%, the default low temperature alarm is 50°F, the
default high temperature alarm is 65°F, the default low humidity alarm is 5%, the default high humidity
alarm is 95%, the defrost feature is disabled, the control will be default to auto change over mode, and
the fan auto/on feature is defaulted to auto. All other settings are to remain as listed above.