Battery cables provide the link between the batteries, equipment, and charging system. The battery cable 

should be sized for the maximum load of the system where the voltage drop on the cable will not exceed 0.2 

volts. To ensure proper connections, please use the wire gauge reference in Sec 3.2.1. Please note: UL and 

NEC electrical cable amperage ratings are lower than the chart below.  

3.2.1 

Wire Gauge Reference 

AWG 

Diameter 

inches (mm) 

Ohms per 

1000ft 

Maximum 

Current (A) 

16 

0.051 (1.29) 

4.016 

22 

14 

0.064 (1.63) 

2.525 

32 

12 

0.081 (2.05) 

1.588 

41 

10 

0.102 (2.59) 

0.999 

55 

0.129 (3.26) 

0.628 

73 

0.162 (4.11) 

0.395 

101 

0.204 (5.19) 

0.249 

135 

0.258 (6.54) 

0.156 

181 

0 (1/0) 

0.325 (8.25) 

0.098 

245 

00 (2/0) 

0.365 (9.27) 

0.078 

283 

000 (3/0) 

0.410 (10.4) 

0.062 

328 

0000 (4/0) 

0.460 (11.68) 

0.049 

380 

3.2.2 

Threaded Terminals 

The BattaMax has two threaded terminals and comes with the necessary bolts and washers to secure a cable 

connection. 

 

Place battery connection cable lug (not included) over the threaded insert of the battery terminal ensuring that 

the cable lug connection is contacting the metal surface of the terminal. Place the flat washer on top of the cable 

lug, followed by the lock washer. Do not place washer between the terminal lead and the battery wire, which 

creates high resistance and can cause terminal meltdown. 

 

Add the hexagonal bolt and tighten to a torque of 98-107 (in-lbs), 11-12 (Nm) 

 

3.2.2.1 

Terminal Protection 

Corrosion can build up on terminals if they are not kept clean and dry. To prevent corrosion, apply a thin coat of 

terminal protector spray that can be purchased through your local automotive parts dealer. 

3.3  C

ONFIGURATION

 

Batteries can be connected in series (increases voltage, maintains ah capacity), in parallel (increases ah 

capacity, maintains voltage), or in a combination of series and parallel. 

3.3.1 

Series Connection 

A series connection will increase the system voltage and the system capacity (Ah) will remain unchanged. 

Summary of Contents for BattaMax BAT-RA12-033

Page 1: ...BattaMax User Manual Revision 3 0 Page 1 of 13 windynation 10 04 2019 BattaMax Absorbent Glass Mat AGM Sealed Lead Acid SLA Batteries BAT RA12 033 BAT RA12 100 User s Manual...

Page 2: ...ies Parallel Connection 7 4 Service and Maintenance 8 4 1 Charging 8 4 1 1 State of Charge SOC 8 4 1 2 Charge Characteristic Curve Standby Use 9 4 1 3 Temperature Compensation 9 4 2 Discharging 9 4 2...

Page 3: ...nd servicing should be referred to qualified service personnel Remove all sources of power photovoltaic wind generator battery chargers etc before servicing or installing Battery Safety Warning Batter...

Page 4: ...0hr 1 80V cell 25oC 35 Ah 106 Ah Nominal Capacity 10hr 1 80V cell 25oC 33 Ah 100 Ah Max Discharge Current 330A 5S 1000A 5S Internal Resistance 10 0m 5 0m Cycle Use 14 6 14 8V 25oC Temp Coefficient 4mV...

Page 5: ...ures there is more chemical activity inside a battery than at lower temperatures The following chart shows the temperature effects to the battery capacity The following chart shows the temperature eff...

Page 6: ...rminals and comes with the necessary bolts and washers to secure a cable connection Place battery connection cable lug not included over the threaded insert of the battery terminal ensuring that the c...

Page 7: ...stem capacity Ah and the system voltage will remain unchanged For example if two 12V batteries with 50Ah of capacity are wired in series the resulting battery bank will be 12V of 100Ah 50Ah 50Ah 100Ah...

Page 8: ...hat higher charge voltage to charge the battery quickly and safely Once the battery is fully charged a somewhat lower voltage is applied to maintain the battery in a fully charged state Important Batt...

Page 9: ...y temperature The temperature should be adjusted by subtracting 0 004 volt per cell from the voltage reading for every 1 C above 25 C or adding 0 004 volt per cell for every 1 C below 25 C 4 2 DISCHAR...

Page 10: ...5 36 0 6 68 20 9 3 50 10 8 1 65V cell 131 9 405 4 103 8 316 7 63 7 190 1 36 8 117 1 22 1 71 1 17 3 52 7 11 7 36 5 6 77 21 1 3 53 10 9 1 60V cell 136 9 407 0 107 0 318 5 65 6 191 5 37 9 118 0 22 8 71 7...

Page 11: ...inter months it is critical that they are kept fully charged at all times 5 2 RECYCLING Batteries that have reached the end of their service life should be returned to a local or regional collection c...

Page 12: ...e 1 year from the date the original purchaser Customer receives the Product the Warranty Period This warranty extends only to the original purchaser The Customer s sole and exclusive remedy and the en...

Page 13: ...RPOSE WITH RESPECT TO ANY PRODUCTS PROVIDED BY WINDY NATION NO ORAL OR WRITTEN INFORMATION OR ADVICE GIVEN BY WINDY NATION ITS DEALERS DISTRIBUTORS AGENTS OR EMPLOYEES SHALL IN ANY WAY INCREASE THE SC...

Reviews: