Smoke control unit
– Type: WSC 308 01
8
Technical data, Smoke central unit Type WSC 308 01
Connection possibilities:
1)
Motors up to 8A.
2)
Smoke detectors, differential heat detectors and/or maximum heat detectors, multi-sensor smoke
detectors (smoke/heat combination detectors), up to 15 units.
3)
Break glass units (primary), up to 6 units (max. current load of the alarm display = 250mA).
4)
Break glass units (secondary), up to 15.
5)
Ventilation buttons with ‚open' indicator, up to 15, any number without ‚open' indicator (max.
current load = 120mA).
6)
Wind/rain detectors with potential free N/O contact (max. current load of the detector = 250mA).
7)
ASC CLOSE function at the smoke detector input (insert ASV module).
Operating/control elements:
The reset button on the control PCB is used to reset a tripped smoke ventilation system and to close the
actuators.
Setting possibilities via slide switch SW1:
SW 1/1 = ON
Maintenance control is activated.
SW 1/1 = OFF
Maintenance control is not activated. Only a coded deactivation is possible following an
activation!
As a control of the activation, the operating LED flashes for 10 sec. If SW1/1 is switched back to OFF again
within this time, the activation process is deleted.
The maintenance control is triggered after the elapse of a 12 month time period. The yellow malfunction LED in
the break glass unit (primary) is lit, and a permanent acoustic alarm signal sounds. Also the green operating
LED is still lit to indicate the absence of a fault. A malfunction message has priority.
SW 1/2 = ON
The transmission of the alarm message (alarm malfunction module 1) is interrupted after 3
minutes.
SW 1/2 = OFF The alarm message (alarm malfunction module 1) is transmitted for as long as an alarm is
tripped.
Setting possibilities via slide switch SW2:
SW 2/1 = ON
The smoke control system trips following a malfunction message from the motor, smoke
detector, SHE switch circuit, over-temperature
SW 2/1 = OFF
The smoke control system does not trip following a malfunction message. The malfunction
message is only displayed by LED`s.
SW 2/2 = ON
The actuators only move OPEN for as long as the ventilation button is pressed (dead man
control).
SW 2/2 = OFF
The actuators move OPEN as soon as the ventilation button is pressed (self-hold).
MALFUNCTION REMEDY:
Diagnosis / monitoring in the smoke control unit:
LED's on the PCB's
Function OK
Malfunction
Diagnosis
Mains (green)
lit
off
Check mains voltage and mains fuse
Operation (green)
lit
off
at any malfunction
Check all functions Temp.
Check temperature fuse for 0 Ohm
Smoke detector (yellow))
off
flashes when interrupted,
is lit after a short circuit
Check wiring and the active end
module
Break glass unit (yellow)
off
flashes when interrupted,
is lit after a short circuit
Check wiring and jumper J1 in the
last or only break glass unit
Motor Circuit (yellow)
off
flashes when interrupted,
after approx. 8 s
Check motor end module and
the motor fuse
Battery/load control
(yellow)
off
see diagnosis battery
see diagnosis battery
Summary of Contents for WSC 308 01
Page 12: ...Smoke control unit Type WSC 308 01 12 Cable plan...
Page 13: ...Smoke control unit Type WSC 308 01 13 WSA 435 Standard wiring diagram...
Page 14: ...Smoke control unit Type WSC 308 01 14 WSA 435 Various wiring diagrams...
Page 15: ...Smoke control unit Type WSC 308 01 15 WSA 435 Various wiring diagrams...