background image

 

Smoke control unit 

– Type: WSC 308 01  

13 

 

W

SA 

 4

3

5

 

Standard wiring diagram

 

 
 

Summary of Contents for WSC 308 01

Page 1: ...mation Operating elements diagnosis LED s fuse review Technical function description Technical data Installation and assembly Cable lengths table Cable plan Wiring diagram Start up and test run CH Win...

Page 2: ...system is exclusively designed for the automatic closing of smoke extraction systems windows flaps or doors Always check that your system meets the valid regulations Pay particular attention to the op...

Page 3: ...tches Dead man s control Diagnosis LEDs Trip following a malfunction N e t z L E D Motor Battery R e s e t S H E C L O S E D Vent OPEN display 120mA Wind rain Manual detector Autom detector External v...

Page 4: ...oke control unit and the red LED in the break glass unit are lit The yellow malfunction LED in the break glass unit flashes The green operating LED s extinguish Resetting a trip caused by high tempera...

Page 5: ...the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped potential free contact in the sensor switches The ventilation functions ar...

Page 6: ...ction by using special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break glass unit All ventilation functions...

Page 7: ...ns screw terminal plug screw terminals 0 5 2 5sqmm Motor screw terminal 0 5 10sqmm Cable monitoring automatic detectors detector circuit with active end module break glass unit detector circuit with e...

Page 8: ...s Also the green operating LED is still lit to indicate the absence of a fault A malfunction message has priority SW 1 2 ON The transmission of the alarm message alarm malfunction module 1 is interrup...

Page 9: ...terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded smoke control units to the break glass unit c...

Page 10: ...the smoke control unit and affix by means of the 4 holes in the building structure Ensure that suitable fastening material is available Note Place sealing washers plastic or similar between the housi...

Page 11: ...ke ventilation system actuator is part of the system component electric motor actuation and does not belong to the electrical installation We recommend in all cases to discuss the type of cable routin...

Page 12: ...Smoke control unit Type WSC 308 01 12 Cable plan...

Page 13: ...Smoke control unit Type WSC 308 01 13 WSA 435 Standard wiring diagram...

Page 14: ...Smoke control unit Type WSC 308 01 14 WSA 435 Various wiring diagrams...

Page 15: ...Smoke control unit Type WSC 308 01 15 WSA 435 Various wiring diagrams...

Page 16: ...ally with an approx 3 mm spacing from the housing edge and firmly press down to the housing bottom b Plug the red connection cable to the and the blue connection to the flat plug of the smoke control...

Page 17: ...will automatically close after 2 minutes e Test the smoke trip and reset close as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow battery LED is OFF T...

Reviews: