Smoke control unit 

– Type: WSC 308 01  

 

Technical function description  WSC 308 01 

 
 
Ventilation functions: 

 

Ventilation OPEN: 

With the dead man's circuit activated (SW2/2 = ON), the actuators only move open for as long as the OPEN 
button of the ventilation button is kept pressed. 
If no dead man's function is activated (SW2/2 = OFF), the actuators open after pressing the OPEN button 
(self hold). 

Display:

 The ventilation open LED in the ventilation button is lit (only with LED integrated in the button). 

 

Ventilation stop: 

The actuators stop when both buttons are pressed. 

Display:

 The ventilation open LED in the ventilation button remains lit (only with LED integrated in the button). 

 

Ventilation closed: 

The actuators close after pressing the CLOSED button. 

Display: 

The ventilation open LED in the ventilation button has extinguished (only with LED integrated in the 

button). 
 

Option: Ventilation time module 

Time setting between 1 and 30 min. Once this time has elapsed, the actuators clo

se after ventilation „OPEN“ 

or ventilation „STOP“. This function is not operative if the setting potentiometer is on the right-hand stop. 
 

Wind/rain CLOSE: 

The actuators close when the wind/rain sensor has tripped (potential free contact in the sensor switches). The 
ventilation functions are out of operation as long as a tripped situation is pending. 
 

Option: Transmission of the wind/rain signal 

The trip signal of the wind/rain sensor can be transmitted potential free to the next smoke control unit 
by plugging in the wind/rain relaying module. 
 

Note: All ventilation functions are locked in the event of a power failure or when an alarm is triggered! 

 

General information: 

 

CLOSE after a power failure: 

Opened actuators will automatically close via the ventilation system 2 minutes after a power failure. 
The motor voltage will be deactivated after another 2 minutes. 
In the event the smoke control system trips, this function will be deactivated. 
 

EMC protection: 

All inputs and outputs are protected from coupled in interferences. 
 

Short-circuit protection: 

All outputs are protected against short-circuit and overload. 
 

Maintenance: 

Smoke control systems must be maintained by the builder at least once per year. 
The maintenance and check of the system must be documented in a test placard in the smoke control unit as 
well as in a logbook. 
 

Summary of Contents for WSC 308 01

Page 1: ...mation Operating elements diagnosis LED s fuse review Technical function description Technical data Installation and assembly Cable lengths table Cable plan Wiring diagram Start up and test run CH Win...

Page 2: ...system is exclusively designed for the automatic closing of smoke extraction systems windows flaps or doors Always check that your system meets the valid regulations Pay particular attention to the op...

Page 3: ...tches Dead man s control Diagnosis LEDs Trip following a malfunction N e t z L E D Motor Battery R e s e t S H E C L O S E D Vent OPEN display 120mA Wind rain Manual detector Autom detector External v...

Page 4: ...oke control unit and the red LED in the break glass unit are lit The yellow malfunction LED in the break glass unit flashes The green operating LED s extinguish Resetting a trip caused by high tempera...

Page 5: ...the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped potential free contact in the sensor switches The ventilation functions ar...

Page 6: ...ction by using special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break glass unit All ventilation functions...

Page 7: ...ns screw terminal plug screw terminals 0 5 2 5sqmm Motor screw terminal 0 5 10sqmm Cable monitoring automatic detectors detector circuit with active end module break glass unit detector circuit with e...

Page 8: ...s Also the green operating LED is still lit to indicate the absence of a fault A malfunction message has priority SW 1 2 ON The transmission of the alarm message alarm malfunction module 1 is interrup...

Page 9: ...terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded smoke control units to the break glass unit c...

Page 10: ...the smoke control unit and affix by means of the 4 holes in the building structure Ensure that suitable fastening material is available Note Place sealing washers plastic or similar between the housi...

Page 11: ...ke ventilation system actuator is part of the system component electric motor actuation and does not belong to the electrical installation We recommend in all cases to discuss the type of cable routin...

Page 12: ...Smoke control unit Type WSC 308 01 12 Cable plan...

Page 13: ...Smoke control unit Type WSC 308 01 13 WSA 435 Standard wiring diagram...

Page 14: ...Smoke control unit Type WSC 308 01 14 WSA 435 Various wiring diagrams...

Page 15: ...Smoke control unit Type WSC 308 01 15 WSA 435 Various wiring diagrams...

Page 16: ...ally with an approx 3 mm spacing from the housing edge and firmly press down to the housing bottom b Plug the red connection cable to the and the blue connection to the flat plug of the smoke control...

Page 17: ...will automatically close after 2 minutes e Test the smoke trip and reset close as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow battery LED is OFF T...

Reviews: